EasyManua.ls Logo

CleaverBrooks CFC-500 - Appendix A: Parameter Glossary; Appendix B: Hydronic Device Parameter Worksheet Example

CleaverBrooks CFC-500
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CB FALCON
750-265 100
APPENDIX B: HYDRONIC DEVICE PARAMETER WORKSHEET EXAMPLE
Table 48. Example of a Completed Device Parameter Worksheet.
Parameter Name
Customer
Choice - Hidden,
Read Only or
Password
protected Minimum Range Default Setting Maximum Range Parameter Units
Burner cycle count Read Only 0 Cycles
Burner run time Read Only 0 Hours
CH pump cycles Read Only 0 Cycles
DHW pump cycles Read Only 0 Cycles
System pump cycles Read Only 0 Cycles
Boiler pump cycles Read Only 0 Cycles
Auxiliary pump cycles Read Only 0 Cycles
Temperature units Read Only A:Fahrenheit
Antishort cycle time Read Only 1m 0s mmm:ss
Alarm silence time Read Only 5m 0s mmm:ss
Burner name Read Only 20 chars
Installation data Read Only 20 chars
OEM identification Read Only 20 chars
Modulation output Hidden B:Demand rate is
in % units
CH maximum modulation
rate
Read Only 100% % | RPM
DHW maximum modulation
rate
Read Only 100% % | RPM
Minimum modulation rate Read Only 0% % | RPM
Prepurge rate Read Only 100% % | RPM
Lightoff rate Read Only 25% % | RPM
Postpurge rate Read Only 25% % | RPM
CH forced rate Read Only 25% % | RPM
CH forced rate time Read Only 1m 0s mmm:ss
DHW forced rate Read Only 25% % | RPM
DHW forced rate time Read Only 120m 0s mmm:ss
Burner switch Read Only Yes/True/On
Firing rate control Read Only A:Automatic firing
Manual firing rate Read Only 25% % | RPM
Analog output hysteresis Read Only 0 20 1 to 10
CH enable Read Only Enabled
CH demand source Read Only D:Sensor & LCI
CH sensor Read Only A:Outlet sensor
CH setpoint Read Only 32°F 0°C 180°F 82°C 240°F 116°C
CH tod setpoint Read Only 32°F 0°C 160°F 71°C 240°F 116°C
CH on hysteresis Read Only 2°F 1°C 15°F 8°C 100°F 56°C
CH off hysteresis Read Only 2°F 1°C 15°F 8°C 100°F 56°C
CH outdoor reset enable Read Only Disabled

Table of Contents