CB FALCON
103 750-265
Annunciator 4 location Read Only A:No annunciation
for this terminal
Annunciator4 short name Read Only A4 3 chars
Annunciator 4 long name Read Only Annunciator4 20 chars
Annunciator 5 location Read Only E:No annunciation
for this terminal
Annunciator5 short name Read Only A5 3 chars
Annunciator 5 long name Read Only Annunciator5 20 chars
Annunciator 6 location Read Only E:No annunciation
for this terminal
Annunciator6 short name Read Only A6 3 chars
Annunciator 6 long name Read Only Annunciator6 20 chars
Annunciator 7 location Read Only E:No annunciation
for this terminal
Annunciator7 short name Read Only A7 3 chars
Annunciator 7 long name Read Only Annunciator7 20 chars
Annunciator 8 location Read Only E:No annunciation
for this terminal
Annunciator8 short name Read Only A8 3 chars
Annunciator 8 long name Read Only Annunciator8 20 chars
PII short name Read Only PII 3 chars
PII long name Read Only Pre-Ignition ILK 20 chars
LCI short name Read Only LCI 3 chars
LCI long name Read Only Load Control Input 20 chars
ILK short name Read Only ILK 3 chars
ILK long name Read Only Interlock 20 chars
DHW enable Read Only Disabled
DHW demand source Read Only A:DHW sensor
only
DHW has priority over CH Read Only No/False/Off
DHW has priority over LL Read Only No/False/Off
DHW priority time Read Only 30m 0s mmm:ss
DHW setpoint Read Only 32°F 0°C 140°F 60°C 240°F 116°C
DHW tod setpoint Read Only 32°F 0°C 120°F 49°C 240°F 116°C
DHW on hysteresis Read Only 2°F 1°C 5°F 3°C 100°F 56°C
DHW off hysteresis Read Only 2°F 1°C 5°F 3°C 100°F 56°C
DHW P gain Read Only 0 50 400
DHW I gain Read Only 0 50 400
DHW D gain Read Only 0 50 400
DHW hysteresis step time Read Only 0m 0s mmm:ss
Outlet high limit setpoint Read Only 32°F 0°C 220°F 104°C 240°F 116°C
Outlet high limit response Read Only [ A B #c #d ] A:Lockout
Stack limit enable Read Only Disabled
Stack limit setpoint Read Only 32°F 0°C 200°F 93°C 500°F 260°C
Stack limit response Read Only [ A #b C #d ] A:Lockout
Table 48. Example of a Completed Device Parameter Worksheet. (Continued)
Parameter Name
Customer
Choice - Hidden,
Read Only or
Password
protected Minimum Range Default Setting Maximum Range Parameter Units