BOILER BOOK CFC-E ENGINEERING DATA
22
Table 10. Safety Relief Valve Information
@125 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 3364
CFC-E 750 3/4” 1" 3364
CFC-E 1000 3/4” 1" 3364
CFC-E 1500 3/4” 1" 3364
CFC-E 2000 3/4” 1" 3364
@100 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 2756
CFC-E 750 3/4” 1" 2756
CFC-E 1000 3/4” 1" 2756
CFC-E 1500 3/4” 1" 2756
CFC-E 2000 3/4” 1" 2756
@80 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 2270
CFC-E 750 3/4” 1" 2270
CFC-E 1000 3/4” 1" 2270
CFC-E 1500 3/4” 1" 2270
CFC-E 2000 3/4” 1" 2270
@75 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 2148
CFC-E 750 3/4” 1" 2148
CFC-E 1000 3/4” 1" 2148
CFC-E 1500 3/4” 1" 2148
CFC-E 2000 3/4” 1" 2148
@60 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 1785
CFC-E 750 3/4” 1" 1785
CFC-E 1000 3/4” 1" 1785
CFC-E 1500 3/4” 1" 1785
CFC-E 2000 1" 1-1/4" 2789
@50 psig
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH)
CFC-E 500 3/4” 1" 1540
CFC-E 750 3/4” 1" 1540
CFC-E 1000 3/4” 1" 1540
CFC-E 1500 3/4” 1" 1540
CFC-E 2000 1" 1-1/4" 2407