5
THE SMART SOLUTION FOR ENERGY EFFICIENCY
ATA11U03
Rev.:09/16/13
Conguration
Conguration
Congurationoptionsenabletheinstallertocongure
thethermostatforaparticularinstallation.These
congurationoptionsarestoredtotheinternal
memorysotheyareretainedthroughapoweroutage.
Theavailabilityofsomecongurationoptionswillbe
dependentuponotherconditionsinthethermostat.
Table 1: Conguration Options Summary
Entering and Exiting Conguration Mode-Pressand
holdthefanbuttonforabout10seconds.Afterthe10
secondperiodtheOptionnumber“02”willappear
ashinginthespacetemperaturelocation.Thevalueof
thecongurationsettingwillbedisplayedinthesetpoint
location.
Theparameterthatischangeablewillbedeterminedby
theashingarea.Theupordownbuttonscanbeused
toselectanewvalue.Themodebuttoncanbeusedto
toggle/movetheselectionbetweentheconguration
optionnumberandthecongurationvalue.Toexitthe
installercongurationscreen,pressthefanbutton.If
nobuttonispressedforthreeminutes,theinstaller
congurationscreenwilltimeoutandthethermostatwill
returntonormaloperation.
Allchangestotheinstallercongurationaresavedas
theyaremade.Thereisnoprovisiontoexittheinstaller
congurationandcancelthechange.Theinstallerwill
havetomanuallychangeacongurationbacktoits
originalvalueto“undo”achange.
Conguration Options
OPTION 02 — REMOTE SENSOR SELECTION — A
remotesensor17B0008N05(forinsideduet),orASW06
(forwall)canbeconnectedtotheS1andS2screw
terminalstosenseeitherremotespace,returnair,
outdoorair,orsupplyairtemperature.
Selection:rA,Od,SA,rS
rA*—Sensereturnairtemperature
*Displayonly,notusedfortemperaturecontrol.
Od*—Senseoutdoorairtemperature
SA*—Sensesupplyairtemperature
rS—Senseremotespacetemperature
Default:rS
Note: Option 02 cannot be changed from the rS setting
if Option 05 is set to either r or Lr.
OPTION 03 — ENGLISH/METRIC—Thisconguration
selectsbe-tweenFahrenheit(F)andCelsius(C)operation.
Selection:F,C
Default:F
OPTION 05 — SPACE TEMPERATURE SENSING —
This selection determines which sensor the control
willuseformeasuringspacetemperature.Space
temperaturecanbesensedinoneofthreeways:the
localsensor(L)locatedonthethermostat,theremote
sensor(r),ortheaverageoflocalandremotesensors(Lr).
Selection:L,r,Lr(Donotuse)
L—Localsensor:Theonboardthermistoristhe
controlpointforthetemperaturecontrolalgorithm.
r—Remotespacesensor:Theremotespace
temperatureisthecontrolpointforthetemperature
control algorithm.
NOTE: This selection is only available if Option 02
indicates that the S1, S2 terminals are sensing a
remote space temperature.
Default:r
� WARNING! �
WARNING! User should not recongure installer set up.
Equipment damage could occur.
� NOTICE �
Wall thermostat requires congurating for on board sensing.
Installer must congure 05 to L unless remote sensor
is used.
Option
Number
Conguration Default
02 Remote Sensor Selection rS
03 English/Metric F
05 Space Temperature Sensing r
07 Equipment DDC Controller OF
11 Deadband between Heating and Cooling Set Points 5
13 Space Temperature Display Adjustment (Offset) 0
15 Auto Mode Availability ON
16 Maximum Cycles Per Hour 4
18 Backlight Conguration OF
20 Outdoor Air Temperature Adjustment (Offset) 0
21 Keypad Lockout OF
26 Minimum Cooling Set Point 60
27 Maximum Heating Set Point 85
39 Temperature Display St
40 Fan Speeds Selection 2