EasyManua.ls Logo

ClimateMaster CCE07 Series - Unit Operating Conditions

ClimateMaster CCE07 Series
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Consoles
Rev.: 5 Nov., 2009B
climatemaster.com
Unit Operating Conditions
Table: 10 TRC Series Typical Operating Pressures and Temperatures (60 Hz I.P. Units)
TRC09 Full Load Cooling - without HWG Active Full Load Heating - without HWG Active
Entering
Water
Temp
°F
Water
Flow
GPM/
Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp Drop
°F
Air Temp
Rise °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp Drop
°F
Air
Temp
Rise °F
DB
30
1.4
2
2.75
126-136
126-136
126-136
161-181
146-166
131-151
17-22
17-22
17-22
8-13
7-12
6-11
19.8-21.8
14.9-16.9
9.9-11.9
21-27
21-27
21-27
74-84
77-87
79-89
278-298
280-300
283-303
6-11
6-11
6-11
4-9
4-9
3-8
6.1-8.1
4.5-6.5
2.8-4.8
18-24
18-24
19-25
50
1.4
2
2.75
132-142
132-142
132-142
215-235
200-220
185-205
10-15
10-15
10-15
8-13
7-12
6-11
18.8-20.8
14.4-16.1
9.4-11.4
20-26
20-26
20-26
104-114
106-116
108-118
309-329
312-332
315-335
8-12
8-12
8-12
7-12
7-12
7-12
9.6-1
1.6
7-9
4.5-6.5
24-30
24-30
25-31
70
1.4
2
2.75
138-148
138-148
137-147
278-298
263-283
248-268
8-13
8-13
8-13
9-14
8-13
7-12
17.7-19.7
13.1-15.1
8.5-10.5
19-25
19-25
19-25
127-137
132-142
138-148
332-352
340-360
341-367
10-15
1
1-16
13-18
10-15
10-15
10-15
12-14
9-10
6.1-8.1
29-35
29-35
30-36
90
1.4
2
2.75
142-152
142-152
142-152
365-385
351-371
337-357
8-13
8-13
8-13
9-14
8-13
7-12
16-18
12-14
8-10
18-24
18-24
18-24
164-174
165-175
167-177
372-392
375-395
379-399
17-22
18-23
19-24
13-18
13-18
13-18
14.5-16.5
11.2-13.2
7.9-9.9
35-41
35-41
36-42
110
1.4
2
2.75
150-160
150-160
150-160
439-459
439-459
439-459
7-12
7-12
7-12
9-14
8-13
7-12
14.2-16.2
10.6-12.6
6.9-8.9
17-23
17-23
17-23
TRC12 Full Load Cooling - without HWG Active Full Load Heating - without HWG Active
Entering
Water
Temp
°F
Water
Flow
GPM/
Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp Drop
°F
Air Temp
Rise °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp Drop
°F
Air
Temp
Rise °F
DB
30
1.75
2.6
3.5
98-108
98-108
99-109
140-160
135-155
127-148
36-41
36-41
36-41
14-19
12-17
10-15
17.1-19.1
12.5-14.5
7.9-9.9
19-25
19-25
19-25
72-82
85-95
78-88
301-321
304-324
308-328
9-14
9-14
9-14
12-17
12-17
12-17
6.5-8.5
4.7-6.7
2.9-4.9
21-27
21-27
22-28
50
1.75
2.6
3.5
118-128
118-128
118-128
215-235
200-220
185-205
22-27
22-27
22-27
14-19
12-17
10-15
18.1-20.1
13.1-15.1
8.1-10.1
20-26
20-26
19-25
100-110
98-108
95-105
337-357
334-354
332-352
10-15
10-15
11-16
15-20
15-20
15-20
9.5-11.5
6.6-8.6
3.8-5.8
26-32
26-32
26-32
70
1.75
2.6
3.5
132-142
132-142
132-142
300-320
263-282
245-265
1
1-16
1
1-16
12-17
12-17
10-15
7-12
17-19
12.6-14.6
8.2-10.2
19-25
19-25
19-25
115-125
112-122
110-120
361-381
360-380
356-376
19-24
20-25
21-26
18-23
18-23
18-23
11.1-13.1
8-10
4.8-6.8
29-35
29-35
29-35
90
1.75
2.6
3.5
138-148
138-148
138-148
366-386
353-373
340-360
9-14
9-14
9-14
11-16
9-14
6-11
15.8-17.8
14.9-16.9
14-16
18-24
18-24
18-24
122-132
123-133
124-134
376-396
378-398
380-400
34-39
36-41
38-43
22-27
22-27
23-28
12.1-14.1
9-11
5.8-7.8
32-38
32-38
32-38
110
1.75
2.6
3.5
145-155
145-155
145-155
453-473
442-462
431-451
9-14
9-14
9-14
9-14
7-12
5-10
14.7-16.7
10.8-12.8
6.8-8.8
16-22
16-22
17-23
NOTE: Table 10 includes the following notes:
• Airfl ow is at nominal (rated) conditions;
• Entering air is based upon 70°F [21°C] DB in heating
and 80/67°F [27/19°C] in cooling;
• Subcooling is based upon head pressure at
compressor service port;
• Cooling air and water values can vary greatly with
changes in humidity level.