Tranquility
®
16
COMPACT (TC) Series
MODELS TCH/V 006 - 60
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N07
Revised: July 7, 2020
Table of Contents
Model Nomenclature – General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
TC - Horizontal – Dimensional Data 20
TCH with WSE – Dimensional Data 22
TC - Horizontal Service Access 24
TC - Vertical Upow – Dimensional Data 25
TCV with WSE – Dimensional Data 27
TC - Vertical Service Access 29
Electrical Data – Standard Unit 30
Electrical Data – High Static Blower 31
Electrical Data – Constant Torque ECM 32
Electrical Data – Constant Volume ECM 33
Electrical – Line Voltage 34
Eletctical – Power & Low Voltage Wiring 35
Electrical – Low Voltage Wiring 36
Electrical – Thermostat Wiring 37
Blower Performance Data – TC006 38
Blower Performance Data – TC009 39
Blower Performance Data – TC012 40
Blower Performance Data – TC015 41
Blower Performance Data – TC018 42
Blower Performance Data – TC024 43
Blower Performance Data – TC030 44
Blower Performance Data – TC036 45
Blower Performance Data – TC041 46
Blower Performance Data – TC042 47
Blower Performance Data – TC048 48
Blower Performance Data – TC060 49
Constant Volume ECM Control 50
Wiring Diagram Matrix 52
DIP Setting Table 53
CXM Controls 54
DXM2 Controls 55
Safety Features – CXM and DXM2 Controls 60
Unit Starting and Operating Conditions 62
Piping System Cleaning and Flushing 63
TC with Waterside Economizer Option 64

Table of Contents

Questions and Answers

  • C
    Crystal HamiltonAug 18, 2025
    How to troubleshoot main power problems in my ClimateMaster Tranquility TCH 012?
    • L
      Linda MayoAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, start by checking the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor. Further, verify that there is 24VAC between R and C on CXM/DXM2. Finally, examine the primary and secondary voltage on the transformer.
  • R
    Ryan TravisAug 23, 2025
    What causes LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) in a ClimateMaster Tranquility TCH 012 Heat Pump?
    • L
      lcollinsAug 23, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it might be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • O
    Olivia CameronAug 26, 2025
    Why does my ClimateMaster Tranquility TCH 012 show LT1 Fault Code 4 (Water coil low temperature limit)?
    • A
      Ashley WoodAug 26, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. Start by checking the pump operation or water valve operation/setting if there is reduced or no water flow in heating. Clean or replace the plugged strainer or filter. Ensure the water flow is adjusted to the proper rate. Check the antifreeze density with a hydrometer to ensure an adequate level. If using antifreeze, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within design parameters. Finally, check the thermistor's temperature and impedance correlation per the chart; replace if it's bad.
  • K
    Kathryn LeachAug 27, 2025
    What does LT2 Fault Code 5 (Air coil low temperature limit) mean on my ClimateMaster Heat Pump?
    • S
      Sarah ScottAug 28, 2025
      If your ClimateMaster Heat Pump is showing an Air coil low temperature limit fault (LT2 Fault Code 5), it could be due to several reasons. First, check for a dirty air filter and clean or replace it if there is reduced or no air flow in cooling. Check the fan motor operation and airflow restrictions. Check the static pressure against the blower table if the external static is too high. Ensure the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), normal airside applications will require 30°F [-1°C] only. Finally, check the thermistor's temperature and impedance correlation per the chart if it's bad.
  • A
    Amy RodriguezAug 30, 2025
    How do I fix Condensate Fault Code 6 on my ClimateMaster Tranquility TCH 012?
    • E
      Elizabeth FrostAug 30, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be caused by a blocked drain. Check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Check for proper piping slope away from the unit to ensure good drainage. Ensure the unit slopes toward the outlet. Check the vent location for poor venting. Check for moisture shorting to the air coil if there's moisture on the sensor. Replace the air filter if it is plugged. Find and eliminate any restrictions to return airflow, and consider increasing the return duct and/or grille size.
  • K
    Kevin AtkinsSep 1, 2025
    What does Over/Under Voltage Code 7 mean for my ClimateMaster Heat Pump?
    • J
      Janice SanchezSep 1, 2025
      If your ClimateMaster Heat Pump is showing Over/Under Voltage Code 7 (Auto resetting), it may be due to under voltage. Check the power supply and 24VAC voltage before and during operation. Also, check the power supply wire size. Check compressor starting and consider if a hard start kit is needed. Verify the 24VAC and unit transformer tap for correct power supply voltage. If it is due to over voltage, check the power supply voltage and 24VAC before and during operation. Also, check the 24VAC and unit transformer tap for correct power supply voltage.
  • L
    Laura KimSep 3, 2025
    What does Unit Performance Sentinel Code 8 mean on my ClimateMaster Tranquility TCH 012?
    • H
      Heidi LopezSep 3, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could be due to the following reasons. In heating mode, if LT2 is greater than 125°F [52°C], check for poor airflow or an overcharged unit. In cooling mode, if LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or airflow.
  • M
    Michelle LeeSep 6, 2025
    Why is my ClimateMaster Tranquility TCH 012 Heat Pump short cycling?
    • L
      lauraromeroSep 6, 2025
      If your ClimateMaster Heat Pump is short cycling, it could be due to a dirty air filter; check and clean the air filter. The unit might be in 'test mode'; reset power or wait 20 minutes for auto exit. The unit may be oversized for the space; check the sizing for the actual load of the space. Check the compressor overload and replace if necessary.
  • W
    wendyperrySep 8, 2025
    What causes only the fan to run on my ClimateMaster Tranquility TCH 012 Heat Pump?
    • M
      Melinda KaufmanSep 8, 2025
      If only the fan is running on your ClimateMaster Heat Pump, ensure the thermostat is set for heating or cooling operation. Check for lockout codes and reset power if necessary. Inspect the compressor overload and replace if needed. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode.
  • J
    Jimmy WilsonSep 10, 2025
    Why does only the compressor run on my ClimateMaster Tranquility TCH 012 Heat Pump?
    • K
      Kimberly DeanSep 12, 2025
      If only the compressor runs on your ClimateMaster Heat Pump, check the G wiring at the heat pump. Jumper G and R for fan operation. Check the fan motor relay by jumpering G and R for fan operation and check for Line voltage across BR contacts. Check the fan power enable relay operation (if present). Check for line voltage at the motor and inspect the capacitor. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode. Set for cooling demand and check 24VAC on RV coil and at CXM/DXM2 board for the reversing valve. Check for ‘O’ RV setup not ‘B’ for thermostat setup. Check O wiring at heat pump and jumper O and R for RV coil ‘click’.

Summary

Model Nomenclature

General Overview

Explains the unit's model designation system for various configurations and options.

General Information

Safety Warnings and Cautions

Details DANGER, WARNING, CAUTION, and NOTICE statements for safe operation and installation.

Horizontal Installation

Vertical Installation

Piping Installation

Water-Loop Heat Pump Applications

Ground-Loop Heat Pump Applications

Ground Loop Pre-Installation and Piping

Instructions for site preparation, underground piping installation, and testing for ground loops.

Ground-Water Heat Pump Applications

Open Loop System and Water Quality

Discusses open loop piping, water quality guidelines, and heat exchanger material selection.

TCH with Left Hand WSE - Dimensional Data

Left Hand WSE Unit Dimensions and Connections

Details cabinet and connection dimensions for TCH models with a left-hand Waterside Economizer.

TCV with Right Hand WSE - Dimensional Data

Right Hand WSE TCV Unit Dimensions

Provides dimensional data for TCV models with a right-hand Waterside Economizer.

TCV with Left Hand WSE - Dimensional Data

Left Hand WSE TCV Unit Dimensions

Details cabinet and connection dimensions for TCV models with a left-hand Waterside Economizer.

Electrical Data - Standard Units

Standard Unit Electrical Specifications

Lists electrical data including voltage, current, and fuse/HACR ratings for standard units.

Electrical Data - High Static Blower

High Static Blower Electrical Specifications

Provides electrical data for units equipped with a high static blower.

Electrical Data - Constant Torque ECM

Constant Torque ECM Electrical Specifications

Lists electrical data for units using Constant Torque ECM blower motors.

Electrical Data - Constant Volume ECM

Constant Volume ECM Electrical Specifications

Provides electrical data for units with Constant Volume ECM blower motors.

Electrical - Line Voltage Wiring

Line Voltage Wiring Procedures

Details field wiring of line voltage, including compliance with codes and conduit use.

Electrical - Power and Low Voltage Wiring

Thermostat and Low Water Temp Connections

Explains thermostat wiring to CXM/DXM2 and field selection of low water temperature limits.

Electrical - Thermostat Wiring

Thermostat Wiring Diagrams (CXM & DXM2)

Provides wiring diagrams for connecting thermostats to CXM and DXM2 control boards.

Constant Volume ECM Control

CV ECM Control Features

Explains features like soft start, ramp down, and airflow selection for CV ECM control.

TC Series Wiring Diagram Matrix

Wiring Diagram Selection Guide

A matrix to select the correct wiring diagram based on model, voltage, and control type.

DIP Setting Tables

Control Board DIP Switch Configurations

Tables showing DIP switch settings for DXM2 WSE and MPC controls.

CXM Controls

CXM Control Features and DIP Switches

Explains CXM control operation, test modes, fault indications, and field configuration options.

DXM2 Controls

DXM2 Control Features and DIP Switches

Details DXM2 control operation, test modes, fault indications, and DIP switch configurations.

DXM2 Control DIP Switch Settings

DXM2 Control Status Indicators

DXM2 Control Start-up Operation

Safety Features - CXM and DXM2 Controls

Compressor Protection Features

Explains anti-short cycle, random start, fault retry, and lockout protection for compressors.

Temperature Limit Safety Features

Details low water and air temperature limits, condensate overflow, and over/under voltage protection.

Additional Safety and Diagnostic Features

Unit Starting and Operating Conditions

Piping System Cleaning and Flushing

Piping System Cleaning and Flushing Procedures

Step-by-step instructions for cleaning and flushing the piping system to ensure proper operation.

TC with Waterside Economizer Option

Unit and System Checkout

Pre-Power System Checkout Checklist

A comprehensive checklist for unit and system verification before powering up the system.

Unit Start-up Procedure

Step-by-Step Start-up Instructions

Detailed procedures for starting up the unit, including air and water flow checks and temperature measurements.

Preventive Maintenance

Water Coil and Filter Maintenance

Guidelines for cleaning and maintaining water coils and filters to ensure performance.

Functional Troubleshooting

Troubleshooting Fault Codes

A table mapping fault codes to possible causes and recommended solutions for unit operation issues.

Performance Troubleshooting

Troubleshooting Performance Issues

Identifies common performance problems like low capacity and high head pressure and their solutions.

Start-Up Log Sheet

Functional Troubleshooting - Cycle Analysis

Heating and Cooling Cycle Analysis Diagrams

Diagrams illustrating points for measuring temperatures and pressures during heating and cooling cycles.

ClimateMaster Tranquility TCH 012 Specifications

General IconGeneral
Model NumberTCH012
CategoryHeat Pump
RefrigerantR-410A
Phase1
Cooling Capacity12, 000 BTU/hr
Liquid Connection Size3/8"
Suction Connection Size5/8"

Related product manuals