Tranquility
®
16
COMPACT (TC) Series
MODELS TCH/V 006 - 60
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N07
Revised: July 7, 2020
Table of Contents
Model Nomenclature – General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
TC - Horizontal – Dimensional Data 20
TCH with WSE – Dimensional Data 22
TC - Horizontal Service Access 24
TC - Vertical Upow – Dimensional Data 25
TCV with WSE – Dimensional Data 27
TC - Vertical Service Access 29
Electrical Data – Standard Unit 30
Electrical Data – High Static Blower 31
Electrical Data – Constant Torque ECM 32
Electrical Data – Constant Volume ECM 33
Electrical – Line Voltage 34
Eletctical – Power & Low Voltage Wiring 35
Electrical – Low Voltage Wiring 36
Electrical – Thermostat Wiring 37
Blower Performance Data – TC006 38
Blower Performance Data – TC009 39
Blower Performance Data – TC012 40
Blower Performance Data – TC015 41
Blower Performance Data – TC018 42
Blower Performance Data – TC024 43
Blower Performance Data – TC030 44
Blower Performance Data – TC036 45
Blower Performance Data – TC041 46
Blower Performance Data – TC042 47
Blower Performance Data – TC048 48
Blower Performance Data – TC060 49
Constant Volume ECM Control 50
Wiring Diagram Matrix 52
DIP Setting Table 53
CXM Controls 54
DXM2 Controls 55
Safety Features – CXM and DXM2 Controls 60
Unit Starting and Operating Conditions 62
Piping System Cleaning and Flushing 63
TC with Waterside Economizer Option 64

Table of Contents

Questions and Answers

  • L
    leemoralesAug 18, 2025
    How to troubleshoot main power problems in my ClimateMaster Tranquility TCH 024 Heat Pump?
    • W
      williamsderrickAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, start by checking the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor. Further, verify that there is 24VAC between R and C on CXM/DXM2. Finally, examine the primary and secondary voltage on the transformer.
  • J
    James KennedyAug 23, 2025
    What causes LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) in a ClimateMaster Tranquility TCH 024 Heat Pump?
    • M
      Matthew AllenAug 23, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it might be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • W
    walshsheriAug 26, 2025
    Why does my ClimateMaster Tranquility TCH 024 Heat Pump show LT1 Fault Code 4 (Water coil low temperature limit)?
    • D
      Dylan LeeAug 26, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. Start by checking the pump operation or water valve operation/setting if there is reduced or no water flow in heating. Clean or replace the plugged strainer or filter. Ensure the water flow is adjusted to the proper rate. Check the antifreeze density with a hydrometer to ensure an adequate level. If using antifreeze, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within design parameters. Finally, check the thermistor's temperature and impedance correlation per the chart; replace if it's bad.
  • E
    Eugene ThompsonAug 27, 2025
    What does LT2 Fault Code 5 (Air coil low temperature limit) mean on my ClimateMaster Heat Pump?
    • A
      Alejandra MorrisonAug 28, 2025
      If your ClimateMaster Heat Pump is showing an Air coil low temperature limit fault (LT2 Fault Code 5), it could be due to several reasons. First, check for a dirty air filter and clean or replace it if there is reduced or no air flow in cooling. Check the fan motor operation and airflow restrictions. Check the static pressure against the blower table if the external static is too high. Ensure the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), normal airside applications will require 30°F [-1°C] only. Finally, check the thermistor's temperature and impedance correlation per the chart if it's bad.
  • G
    glenn75Aug 30, 2025
    How do I fix Condensate Fault Code 6 on my ClimateMaster Heat Pump?
    • J
      Jimmy LopezAug 30, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be caused by a blocked drain. Check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Check for proper piping slope away from the unit to ensure good drainage. Ensure the unit slopes toward the outlet. Check the vent location for poor venting. Check for moisture shorting to the air coil if there's moisture on the sensor. Replace the air filter if it is plugged. Find and eliminate any restrictions to return airflow, and consider increasing the return duct and/or grille size.
  • M
    Manuel White PhDSep 1, 2025
    What does Over/Under Voltage Code 7 mean for my ClimateMaster Heat Pump?
    • J
      Jaclyn Harris DVMSep 1, 2025
      If your ClimateMaster Heat Pump is showing Over/Under Voltage Code 7 (Auto resetting), it may be due to under voltage. Check the power supply and 24VAC voltage before and during operation. Also, check the power supply wire size. Check compressor starting and consider if a hard start kit is needed. Verify the 24VAC and unit transformer tap for correct power supply voltage. If it is due to over voltage, check the power supply voltage and 24VAC before and during operation. Also, check the 24VAC and unit transformer tap for correct power supply voltage.
  • G
    gthompsonSep 3, 2025
    What does Unit Performance Sentinel Code 8 mean on my ClimateMaster Heat Pump?
    • Q
      qsnyderSep 3, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could be due to the following reasons. In heating mode, if LT2 is greater than 125°F [52°C], check for poor airflow or an overcharged unit. In cooling mode, if LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or airflow.
  • J
    Johnathan TaylorSep 6, 2025
    Why is my ClimateMaster Heat Pump short cycling?
    • L
      Lisa HughesSep 6, 2025
      If your ClimateMaster Heat Pump is short cycling, it could be due to a dirty air filter; check and clean the air filter. The unit might be in 'test mode'; reset power or wait 20 minutes for auto exit. The unit may be oversized for the space; check the sizing for the actual load of the space. Check the compressor overload and replace if necessary.
  • J
    Jeremy MoranSep 8, 2025
    What causes only the fan to run on my ClimateMaster Tranquility TCH 024 Heat Pump?
    • T
      Troy BartlettSep 8, 2025
      If only the fan is running on your ClimateMaster Heat Pump, ensure the thermostat is set for heating or cooling operation. Check for lockout codes and reset power if necessary. Inspect the compressor overload and replace if needed. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode.
  • C
    Christian SummersSep 10, 2025
    Why does only the compressor run on my ClimateMaster Heat Pump?
    • M
      Mallory ThompsonSep 12, 2025
      If only the compressor runs on your ClimateMaster Heat Pump, check the G wiring at the heat pump. Jumper G and R for fan operation. Check the fan motor relay by jumpering G and R for fan operation and check for Line voltage across BR contacts. Check the fan power enable relay operation (if present). Check for line voltage at the motor and inspect the capacitor. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode. Set for cooling demand and check 24VAC on RV coil and at CXM/DXM2 board for the reversing valve. Check for ‘O’ RV setup not ‘B’ for thermostat setup. Check O wiring at heat pump and jumper O and R for RV coil ‘click’.

Summary

Model Nomenclature - General Overview

Model Nomenclature - General Overview

Explains the coding system for unit model identification.

General Information

Safety

Covers warnings, cautions, and notices for safe installation and operation.

Inspection

Procedures for checking equipment upon receipt for damage or shortages.

Storage

Guidelines for proper storage of units to prevent damage.

Unit Protection

Recommendations for protecting units on the job site from damage.

Unit Physical Data

Horizontal Installation

Horizontal Unit Location

Guidance on selecting appropriate locations for horizontal unit installation.

Mounting Horizontal Units

Instructions for suspending horizontal units using hanger brackets.

Horizontal Installation - Field Conversion of Air Discharge

Side to Back Discharge Conversion

Steps to convert the air discharge from side to back.

Horizontal Installation, Contd.

Condensate Piping - Horizontal Units

Guidelines for installing the condensate drain line for horizontal units.

Duct System Installation

Critical considerations for sizing and designing duct systems for optimal airflow.

Vertical Installation

Vertical Unit Location

Guidance on selecting appropriate locations for vertical unit installation.

Piping Installation

Water-Loop Heat Pump Applications

Ground-Loop Heat Pump Applications

Ground-Water Heat Pump Applications

Water Quality Standards

TC - Horizontal - Dimensional Data

TC - Horizontal Service Access

TC - Vertical Upflow - Dimensional Data

TC - Vertical Service Access

Electrical Data - Standard Unit

Electrical Data - High Static Blower

Electrical Data - Constant Torque ECM

Electrical Data - Constant Volume ECM

Electrical - Line Voltage

Electrical - Power & Low Voltage Wiring

Electrical - Low Voltage Wiring

Electrical - Thermostat Wiring

Blower Performance Data - TC006

Blower Performance Data - TC006

Performance data for TC006 model, showing airflow at various static pressures.

Blower Performance Data - TC015

Blower Performance Data - TC015

Performance data for TC015 model, showing airflow versus static pressure.

Blower Performance Data - TC030

Blower Performance Data - TC030

Performance data for TC030 model, showing airflow versus static pressure.

Blower Performance Data - TC060

Blower Performance Data - TC060

Performance data for TC060 model, indicating airflow across various static pressures.

Constant Volume ECM Control

TC Series Wiring Diagram Matrix

DIP Setting Table

CXM Controls

DXM2 Controls

Safety Features - CXM and DXM2 Controls

Piping System Cleaning and Flushing

Unit and System Checkout

Unit Start-up Procedure

Unit Operating Conditions

Preventive Maintenance

Functional Troubleshooting

Start-Up Log Sheet

Functional Troubleshooting

Functional Troubleshooting

Analysis of heating/cooling cycle issues and refrigerant troubleshooting.

Warranty (U.S. & Canada)

Warranty (U.S. & Canada)

Outlines the terms and conditions of the limited express warranty for US and Canada.

Warranty (International)

Warranty (International)

Details the limited express warranty terms for international product purchases.

Revision History

Revision History

Log of document updates and changes made over time.

ClimateMaster Tranquility TCH 024 Specifications