Tranquility
®
16
COMPACT (TC) Series
MODELS TCH/V 006 - 60
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N07
Revised: July 7, 2020
Table of Contents
Model Nomenclature – General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
TC - Horizontal – Dimensional Data 20
TCH with WSE – Dimensional Data 22
TC - Horizontal Service Access 24
TC - Vertical Upow – Dimensional Data 25
TCV with WSE – Dimensional Data 27
TC - Vertical Service Access 29
Electrical Data – Standard Unit 30
Electrical Data – High Static Blower 31
Electrical Data – Constant Torque ECM 32
Electrical Data – Constant Volume ECM 33
Electrical – Line Voltage 34
Eletctical – Power & Low Voltage Wiring 35
Electrical – Low Voltage Wiring 36
Electrical – Thermostat Wiring 37
Blower Performance Data – TC006 38
Blower Performance Data – TC009 39
Blower Performance Data – TC012 40
Blower Performance Data – TC015 41
Blower Performance Data – TC018 42
Blower Performance Data – TC024 43
Blower Performance Data – TC030 44
Blower Performance Data – TC036 45
Blower Performance Data – TC041 46
Blower Performance Data – TC042 47
Blower Performance Data – TC048 48
Blower Performance Data – TC060 49
Constant Volume ECM Control 50
Wiring Diagram Matrix 52
DIP Setting Table 53
CXM Controls 54
DXM2 Controls 55
Safety Features – CXM and DXM2 Controls 60
Unit Starting and Operating Conditions 62
Piping System Cleaning and Flushing 63
TC with Waterside Economizer Option 64

Table of Contents

Questions and Answers

  • V
    Valerie BaileyAug 18, 2025
    How to troubleshoot main power problems in my ClimateMaster Tranquility TCH 018?
    • V
      Victoria VelezAug 18, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, start by checking the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor. Further, verify that there is 24VAC between R and C on CXM/DXM2. Finally, examine the primary and secondary voltage on the transformer.
  • S
    Scott CollinsAug 23, 2025
    What causes LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) in a ClimateMaster Tranquility TCH 018?
    • S
      Sharon MorrisonAug 23, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it might be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • M
    Michael ArnoldAug 26, 2025
    Why does my ClimateMaster Tranquility TCH 018 show LT1 Fault Code 4 (Water coil low temperature limit)?
    • A
      Aaron BurnsAug 26, 2025
      If your ClimateMaster Heat Pump displays a Water coil low temperature limit fault (LT1 Fault Code 4), it could be due to several reasons. Start by checking the pump operation or water valve operation/setting if there is reduced or no water flow in heating. Clean or replace the plugged strainer or filter. Ensure the water flow is adjusted to the proper rate. Check the antifreeze density with a hydrometer to ensure an adequate level. If using antifreeze, clip the JW3 jumper for antifreeze (10°F [-12°C]) use. Ensure the water temperature is within design parameters. Finally, check the thermistor's temperature and impedance correlation per the chart; replace if it's bad.
  • B
    brandy22Aug 27, 2025
    What does LT2 Fault Code 5 (Air coil low temperature limit) mean on my ClimateMaster Tranquility TCH 018 Heat Pump?
    • J
      Javier ConwayAug 27, 2025
      If your ClimateMaster Heat Pump is showing an Air coil low temperature limit fault (LT2 Fault Code 5), it could be due to several reasons. First, check for a dirty air filter and clean or replace it if there is reduced or no air flow in cooling. Check the fan motor operation and airflow restrictions. Check the static pressure against the blower table if the external static is too high. Ensure the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), normal airside applications will require 30°F [-1°C] only. Finally, check the thermistor's temperature and impedance correlation per the chart if it's bad.
  • J
    jnixonAug 29, 2025
    How do I fix Condensate Fault Code 6 on my ClimateMaster Tranquility TCH 018?
    • K
      Kimberly HesterAug 30, 2025
      If your ClimateMaster Heat Pump displays Condensate Fault Code 6, it could be caused by a blocked drain. Check for blockage and clean the drain. Inspect the trap dimensions and ensure its location is ahead of the vent. Check for proper piping slope away from the unit to ensure good drainage. Ensure the unit slopes toward the outlet. Check the vent location for poor venting. Check for moisture shorting to the air coil if there's moisture on the sensor. Replace the air filter if it is plugged. Find and eliminate any restrictions to return airflow, and consider increasing the return duct and/or grille size.
  • A
    Abigail HoganSep 1, 2025
    What does Over/Under Voltage Code 7 mean for my ClimateMaster Heat Pump?
    • C
      Cassandra SmithSep 1, 2025
      If your ClimateMaster Heat Pump is showing Over/Under Voltage Code 7 (Auto resetting), it may be due to under voltage. Check the power supply and 24VAC voltage before and during operation. Also, check the power supply wire size. Check compressor starting and consider if a hard start kit is needed. Verify the 24VAC and unit transformer tap for correct power supply voltage. If it is due to over voltage, check the power supply voltage and 24VAC before and during operation. Also, check the 24VAC and unit transformer tap for correct power supply voltage.
  • B
    Beth EllisSep 3, 2025
    What does Unit Performance Sentinel Code 8 mean on my ClimateMaster Tranquility TCH 018 Heat Pump?
    • E
      Elizabeth ShepherdSep 3, 2025
      If your ClimateMaster Heat Pump displays Unit Performance Sentinel Code 8, it could be due to the following reasons. In heating mode, if LT2 is greater than 125°F [52°C], check for poor airflow or an overcharged unit. In cooling mode, if LT1 is greater than 125°F [52°C] or LT2 is less than 40ºF [4ºC], check for poor water flow or airflow.
  • R
    russelldavidSep 5, 2025
    Why is my ClimateMaster Tranquility TCH 018 Heat Pump short cycling?
    • J
      Joe MayerSep 5, 2025
      If your ClimateMaster Heat Pump is short cycling, it could be due to a dirty air filter; check and clean the air filter. The unit might be in 'test mode'; reset power or wait 20 minutes for auto exit. The unit may be oversized for the space; check the sizing for the actual load of the space. Check the compressor overload and replace if necessary.
  • E
    elizabethglennSep 8, 2025
    What causes only the fan to run on my ClimateMaster Tranquility TCH 018?
    • B
      Bobby SummersSep 8, 2025
      If only the fan is running on your ClimateMaster Heat Pump, ensure the thermostat is set for heating or cooling operation. Check for lockout codes and reset power if necessary. Inspect the compressor overload and replace if needed. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode.
  • B
    bakerjacquelineSep 10, 2025
    Why does only the compressor run on my ClimateMaster Tranquility TCH 018 Heat Pump?
    • J
      Jennifer EllisSep 12, 2025
      If only the compressor runs on your ClimateMaster Heat Pump, check the G wiring at the heat pump. Jumper G and R for fan operation. Check the fan motor relay by jumpering G and R for fan operation and check for Line voltage across BR contacts. Check the fan power enable relay operation (if present). Check for line voltage at the motor and inspect the capacitor. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode. Set for cooling demand and check 24VAC on RV coil and at CXM/DXM2 board for the reversing valve. Check for ‘O’ RV setup not ‘B’ for thermostat setup. Check O wiring at heat pump and jumper O and R for RV coil ‘click’.

Summary

Model Nomenclature Overview

Horizontal Unit Installation

Horizontal Unit Mounting

Instructions for physically mounting horizontal units using hanger brackets.

Vertical Unit Installation

Vertical Unit Location Guidelines

Guidelines for selecting an appropriate indoor location for vertical unit installation.

Piping Installation Guidelines

Supply and Return Piping Installation

Guidelines for installing supply and return piping, including bend radii and torque.

Ground-Loop Heat Pump Applications

Line Voltage Wiring Guidelines

Power & Low Voltage Wiring

Constant Volume ECM Control

CXM Control Operations

DXM2 Control Operations

CXM;DXM2 Control Safety Features

Anti-Short Cycle Protection

Protection mechanism to prevent rapid compressor cycling.

Unit Operating Conditions

Unit Start-Up Procedure

Unit Start-Up Procedure Steps

Step-by-step guide for performing unit start-up tests and checks.

Functional Troubleshooting Guide

Troubleshooting Faults Table