Tranquility
®
Compact
Belt Drive (TCH/V) Series
Models TCH072 - 120
TCV072 - 300
60Hz - HFC-410A
Installation, Operation
& Maintenance
97B0084N01
Revised: July 25, 2017
Table of Contents
Model Nomenclature 3
General Information 4
TCH Physical Data
(includes unit w/WSE) 6
TCV Physical Data
(includes unit w/WSE) 9
Horizontal Installation 16
TCH Field Conversion of Air Discharge 18
Vertical Installation 21
TCV Field Conversion of Air Discharge 22
TCV072-240 Field Conversion of Air Discharge 23
TCV300 Field Conversion of Air Discharge 26
TCV Field Conversion of Control Box 29
TCV Field Conversion of Water Connections 30
Vertical Condensate Installation 31
Piping Installation 32
Water-Loop Heat Pump Applications 33
Ground-Loop Heat Pump Applications 34
Ground-Water Heat Pump Applications 36
Water Quality Standards 38
Electrical - Line Voltage 39
Electrical - Power Wiring 41
Electrical - Power & Low Voltage Wiring 42
Electrical - Thermostat Wiring 44
Typical Wiring Diagram - TCH/V Units with CXM 45
CXM Controls 49
DXM Controls 50
Safety Features 52
CXM and DXM Controls 53
Blower Adjustment 54
Tensioning V-Belt Drives 55
Blower Sheave Information 56
TCH/V 072 Blower Performance 57
TCH/V 096 Blower Performance 58
TCH/V 120 Blower Performance 60
Blower Performance Data – TCV160 Standard Unit 62
Blower Performance Data – TCV192 Standard Unit 63
Blower Performance Data – TCV240 Standard Unit 64
Blower Performance Data – TCV240 Standard Unit 65
Blower Performance Data – TCV300 Standard Unit 66
Unit Starting and Operating Conditions 67
Piping System Cleaning and Flushing 68
Unit Starting and Operating Conditions 69
Unit Start-Up Procedure 70
Unit Operating Conditions 72
Start-Up Log Sheet 73
Preventive Maintenance 74
Circuit Diagram with Safety Devices 75
Functional Troubleshooting 76
Performance Troubleshooting 77
Warranty (U.S. & Canada) 79
Revision History 80

Table of Contents

Questions and Answers

  • C
    clarkandrewAug 18, 2025
    How to troubleshoot ClimateMaster Tranquility TCH Heat Pump main power problems?
    • L
      Lee MooreAug 18, 2025
      To troubleshoot main power issues with your ClimateMaster Heat Pump, check the line voltage circuit breaker and disconnect. Verify line voltage between L1 and L2 on the contactor. Also, check for 24VAC between R and C on the CXM/DXM, and inspect the primary/secondary voltage on the transformer.
  • S
    Sandra WalshAug 20, 2025
    What causes high pressure fault (HP Fault Code 2) in a ClimateMaster Tranquility TCH?
    • K
      Kelly JohnsonAug 21, 2025
      A high-pressure fault in your ClimateMaster Heat Pump can be caused by reduced or no water flow in cooling, so check pump or valve operation/setting and adjust water flow to the proper rate. If the water temperature is out of range in cooling, bring it within design parameters. Reduced or no air flow in heating can also cause this, so check for a dirty air filter and clean or replace it. Check fan motor operation and airflow restrictions. Also, check for a dirty air coil, too high of external static (check static vs blower table), and air temperature out of range in heating (bring return air temp within design parameters). Check superheat/subcooling vs typical operating condition table. Finally, check switch continuity and operation, and replace if necessary.
  • V
    Vanessa MosleyAug 23, 2025
    Why does my ClimateMaster Heat Pump show fault code 6, Condensate?
    • C
      cnelsonAug 23, 2025
      The Condensate Fault Code 6 on your ClimateMaster Heat Pump indicates a blocked drain (check for blockage and clean the drain), an improper trap (check trap dimensions and location ahead of vent), or poor drainage (check for piping slope away from unit). Check slope of unit toward outlet. Check vent location for poor venting. Check for moisture shorting to air coil. Replace air filter if plugged. Find and eliminate restriction. Increase return duct and/or grille size if there is Restricted Return Air Flow.
  • D
    dorseybrookeAug 26, 2025
    What does fault code 4 (LT1 Water coil low temperature limit) mean on my ClimateMaster Tranquility TCH?
    • A
      anna40Aug 26, 2025
      Fault Code 4 on your ClimateMaster Heat Pump indicates a low water coil temperature limit. This can be due to reduced or no water flow in heating, so check pump operation or water valve operation/setting. Look for a plugged strainer or filter and clean or replace it. Ensure proper water flow and adjust to the correct rate. Check antifreeze density with a hydrometer if the antifreeze level is inadequate. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -2°C]), clip JW3 jumper for antifreeze (10°F [-12°C]) use. Bring water temperature within design parameters if it is out of range. Check temperature and impedance correlation per chart.
  • W
    whitneywolfeAug 27, 2025
    What does fault code 5 (LT2 Air coil low temperature limit) mean on my ClimateMaster Tranquility TCH Heat Pump?
    • M
      matthewvillarrealAug 27, 2025
      Fault Code 5 on your ClimateMaster Heat Pump signals a low air coil temperature limit. This could be due to reduced or no air flow in cooling, so check for a dirty air filter and clean or replace it. Check fan motor operation and airflow restrictions. If the external static is too high, check the static vs blower table. If the air temperature is out of range, ensure the entering air temperature is within design parameters. If the temperature limit setting is improper (30°F vs 10°F [-1°C vs -12°C]), normal airside applications will require 30°F [-1°C] only. Check temperature and impedance correlation per chart.
  • Z
    zryanAug 29, 2025
    What causes fault code 3 (Low Pressure / Loss of Charge) on a ClimateMaster Heat Pump?
    • O
      Olivia MckeeAug 30, 2025
      Fault Code 3 on your ClimateMaster Heat Pump indicates low pressure or loss of charge. This can be caused by insufficient charge, so check for refrigerant leaks. Also, check charge and start-up water flow.
  • O
    ochandlerSep 1, 2025
    What to do if my ClimateMaster Heat Pump only runs the fan?
    • C
      chavezlindsaySep 1, 2025
      If your ClimateMaster Heat Pump only runs the fan, ensure the thermostat is set for heating or cooling. Check for lockout codes and reset power. Examine the compressor overload and replace it if necessary. Also, inspect the thermostat wiring at the heat pump, and try jumpering Y and R for compressor operation in test mode.
  • J
    Jacob FoxSep 3, 2025
    What to do if my ClimateMaster Tranquility TCH Heat Pump unit short cycles?
    • L
      Lisa RiveraSep 3, 2025
      If your ClimateMaster Heat Pump is short cycling, check and clean the air filter. Reset the power or wait 20 minutes to exit 'test mode'. Also, the unit may be oversized for the space, so check the sizing for the actual load. Inspect the compressor overload and replace if necessary.
  • E
    elijahpriceSep 6, 2025
    What to do if my ClimateMaster Tranquility TCH only compressor runs?
    • K
      Katrina ThompsonSep 6, 2025
      If only the compressor runs on your ClimateMaster Heat Pump, check the G wiring at the heat pump and jumper G and R for fan operation. Jumper G and R for fan operation, and check for line voltage across BR contacts. Check the fan power enable relay operation (if present). Check for line voltage at the motor and inspect the capacitor. Also, check the thermostat wiring at the heat pump, and try jumpering Y and R for compressor operation in test mode. Set for cooling demand and check 24VAC on RV coil and at CXM/DXM board. If the RV is stuck, run high pressure up by reducing water flow and while operating engage and disengage RV coil voltage to push valve. Check for ‘O’ RV setup not ‘B’. Check O wiring at heat pump. Jumper O and R for RV coil ‘click’.
  • T
    Travis RobertsonSep 8, 2025
    What does code 8 (Unit Performance Sentinel) mean on my ClimateMaster Tranquility TCH Heat Pump?
    • E
      eatonstevenSep 8, 2025
      Code 8 (Unit Performance Sentinel) on your ClimateMaster Heat Pump indicates an issue. In heating mode (LT2>125°F [52°C]), check for poor air flow or an overcharged unit. In cooling mode (LT1>125°F [52°C] OR LT2< 40ºF [4ºC]), check for poor water flow or air flow.

Summary

General Information

Safety

Explains DANGER, WARNING, CAUTION, NOTICE definitions and refrigerant handling.

TCV 300 with WaterSide Economizer

Dimensional Data Table

Provides dimensions for TCV300 with WSE.

Horizontal Installation

Horizontal Unit Location

Discusses optimal indoor placement and service access for horizontal units.

Mounting Horizontal Units

Details the factory-attached hanger brackets and field installation process.

Horizontal Units Condensate Piping

Explains proper pitching and trap installation for condensate drainage.

Duct System Installation

Covers guidelines for sizing, airflow, and insulation of ductwork.

TCH Field Conversion of Air Discharge

Side to Back Discharge Conversion

Provides step-by-step instructions for converting air discharge from side to back.

Back to Side Discharge Conversion

Outlines reversing the side-to-back conversion steps.

Vertical Installation

Vertical Location and Access

Discusses optimal indoor placement and service access for vertical units.

Duct System Design & Installation Guidelines

Provides application guidelines for TC units and ductwork.

TCV Field Conversion of Air Discharge

TCV072-240 Pictorally Shown Top Discharge Steps to Convert to Straight Discharge

Illustrates steps for converting TCV072-120 and TCV160-240 from top to straight discharge.

TCV300 Top Discharge Steps to Convert to Straight Discharge

Illustrates steps for converting TCV300 from top to straight discharge.

TCV Field Conversion of Control Box

Overview and Preparation

Explains control box relocation and preparation steps for conversion.

TCV Field Conversion of Water Connections

Side to Back Discharge Conversion

Details steps for converting water connections to the opposite side.

Vertical Condensate Installation

Condensate Piping - TCV

Explains condensate line setup, trap, vent, and pitching for TCV units.

Piping Installation

Installation of Supply and Return Piping

Covers guidelines for supply/return piping, valves, and hose kits.

Water-Loop Heat Pump Applications

Commercial Water Loop Applications

Discusses commercial systems, air elimination, and piping material recommendations.

Water loop heat pump (cooling tower;boiler) systems

Explains system loop temperatures and cooling tower requirements.

Ground-Loop Heat Pump Applications

Pre-Installation

Covers locating underground utilities and marking piping for new construction.

Piping Installation

Details earth loop piping material, fittings, and flow rates.

Antifreeze

Explains antifreeze requirements, types, and concentration calculations.

Ground-Water Heat Pump Applications

Open Loop - Ground Water Systems

Describes open loop piping, shut-off valves, and material compatibility.

Electrical - Line Voltage

Electrical - Power Wiring

Electrical - Power & Low Voltage Wiring

ELECTRICAL - LOW VOLTAGE WIRING

Details thermostat connection to CXM/DXM boards and low voltage wiring.

Electrical - Thermostat Wiring

Thermostat Installation

Provides guidelines for thermostat location and mounting.

CXM Controls

DXM Controls

Field Selectable Inputs

Explains Test mode and Retry mode for DXM control diagnostics.

Field Configuration Options

Details jumper settings for temperature limits and alarm relay.

DIP Switches

Explains DIP switch configurations for DXM operation.

DIP Package #1 (S1) Settings

Covers UPS disable, compressor staging, and thermostat type selections.

DIP Package #2 (S2) Settings

Details accessory relay personality and fan mode selections.

Safety Features

Safety Features - CXM;DXM Control

Explains safety features protecting compressor and components from improper operation.

CXM and DXM Controls

Diagnostic Features

Details how LEDs on CXM/DXM boards indicate status and faults.

CXM;DXM Control Start-up Operation

Outlines initial start-up sequence including delays and protection.

Blower Adjustment

Sheave Adjustment

Details adjusting the variable sheave drive for airflow and ESP.

Belt Tensioning Procedure - TCH;V

Provides step-by-step instructions for tensioning belts.

Unit Starting and Operating Conditions

Operating Limits

Defines operating limits for air and water based on temperature and humidity.

Unit Checkout

Lists critical checks before powering the system, including voltage, wiring, and components.

System Checkout

Details checks for water temperature, pH, flushing, and controls after system flush.

Piping System Cleaning and Flushing

Unit Start-Up Procedure

Unit Operating Conditions

Preventive Maintenance

Circuit Diagram with Safety Devices

Functional Troubleshooting

Performance Troubleshooting

Insufficient capacity; Not cooling or heating

Covers causes for reduced capacity or lack of cooling/heating.

Functional Troubleshooting - I-P Units

ClimateMaster Tranquility TCH Series Specifications

General IconGeneral
TypeWater Source Heat Pump
RefrigerantR-410A
Compressor TypeScroll
StagesSingle or Two-Stage
ModelTCH Series
Cooling Capacity6, 000 - 72, 000 BTU/h (0.5 to 6 tons, nominal)
Heating Capacity9, 000 to 66, 000 BTU/h
Voltage460V
ConfigurationHorizontal or Vertical
DimensionsVaries by model
Unit WeightVaries by model