17
BRA2 - BRN2 EN
GENERAL TECHNICAL DATA
I A
BRN2 without hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
Heating capacity 1 [kW] 6,76 8,37 10,5 12,9 6,73 8,3 10,00 13,4 14,8 17,3
Power consumption 1 [kW] 2,25 2,84 3,48 4,35 2,24 2,69 3,23 4,47 4,67 5,58
COP 1 3,01 2,95 3,01 2,97 3,01 3,08 3,10 2,99 3,17 3,10
Cooling capacity 2 [kW] 4,81 5,89 7,29 9,6 4,80 5,99 7,35 10,0 11,1 13,0
Power consumption 2 [kW] 1,96 2,39 3,27 3,81 1,92 2,27 2,99 3,95 4,42 4,95
EER 2 2,45 2,46 2,23 2,51 2,50 2,64 2,46 2,52 2,51 2,63
ESEER 1 3,07 3,05 2,87 3,03 3,09 3,29 2,99 3,09 2,85 3,11
Flow-rate 1 m3/h 1,16 1,44 1,80 2,22 1,16 1,43 1,72 2,30 2,55 2,98
Pressure drop 1 kPa 10 12 13 23 10 12 12 25 24 24
Flow-rate 2 m
3
/h 0,83 1,01 1,25 1,64 0,83 1,03 1,26 1,71 1,91 2,24
Pressure drop 2 kPa 5 6 6 13 5 6 6 14 14 14
Sound power 4 [dBA] 75 75 75 77 75 75 75 77 77 77
Power supply V-N/Ph-Hz 230-1N-50 400-3N-50
No. of compressors 1 1 1 1 1 1 1 1 1 1
No. of circuits 1 1 1 1 1 1 1 1 1 1
Type of compressor Scroll
No. of fans 1 1 1 2 1 1 1 2 2 2
Air flow-rate 1 [m
3
/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350
No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1
Type of system heat exchanger PIASTRE
System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
BRN2 with hydronic kit 0021 0025 0031 0041 0021 0025 0031 0041 0051 0061
Heating capacity 1 [kW] 6,72 8,32 10,4 12,8 6,68 8,2 9,99 13,3 14,8 17,2
Power consumption 1 [kW] 2,18 2,75 3,38 4,22 2,17 2,61 3,14 4,38 4,57 5,46
COP 1 3,08 3,02 3,08 3,03 3,08 3,16 3,18 3,04 3,24 3,15
Cooling capacity 2 [kW] 4,83 5,93 7,33 9,6 4,82 6,03 7,39 10,0 11,2 13,1
Power consumption 2 [kW] 1,92 2,34 3,19 3,76 1,88 2,22 2,91 3,88 4,38 4,85
EER 2 2,51 2,53 2,30 2,56 2,56 2,72 2,54 2,58 2,56 2,70
ESEER 1 3,17 3,17 2,97 3,09 3,19 3,43 3,09 3,14 2,93 3,20
Flow-rate 1 m
3
/h 1,16 1,43 1,79 2,20 1,15 1,42 1,72 2,29 2,55 2,96
Available pressure head 1 kPa 66 58 48 46 66 58 51 44 44 40
Flow-rate 2 m
3
/h 0,83 1,02 1,26 1,65 0,83 1,04 1,27 1,72 1,93 2,25
Available pressure head 2 kPa 74 73 67 56 74 73 67 55 55 55
Sound power [dBA] 75 75 75 77 75 75 75 77 77 77
Power supply V-N/Ph-Hz 230-1N-50 400-3N-50
No. of compressors 1 1 1 1 1 1 1 1 1 1
No. of circuits 1 1 1 1 1 1 1 1 1 1
Type of compressor Scroll
No. of fans 1 1 1 2 1 1 1 2 2 2
Air flow-rate [m
3
/h] 3000 3400 3400 6450 3000 3400 3400 6450 6000 6350
No. of system heat exchangers 1 1 1 1 1 1 1 1 1 1
Type of system heat exchanger PLATE
System water heat exchanger content l 2 2 2 2 2 2 2 2 2 3
(1) outside air 7°C; condenser water in/out 40/45°C
(2) outside air 35°C; evaporator water IN/OUT 12/7°C
(3) maximum and minimum operating pressure refer to activation of the pressure switches
(4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1
Performance in accordance with EN 14511:2013
(1) outside air 7°C; condenser water in/out 40/45°C
(2) outside air 35°C; evaporator water IN/OUT 12/7°C
(3) maximum and minimum operating pressure refer to activation of the pressure switches
(4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1
Performance in accordance with EN 14511:2013