EasyManua.ls Logo

CLIVET EVH-X SPACE 10.1 - Water Circuit Start-up Sequence

CLIVET EVH-X SPACE 10.1
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
EVH-X SPACE 2.1 - 12.1
M0SM10N17-03
Operation sequence
Before starting the unit pump :
1 Close all vent valves in the high points of the
unit hydraulic circuit.
2 Close all drain valves in the low points of the
unit hydraulic circuit
Exchangers
Pumps
collectors
storage tanks
3 Carefully wash the system with clean water:
use the bypass to exclude the exchanger from
the flow (diagram on previous page) fill and
drain the system several times.
4 fill and drain the system several times.
5 Apply additives to prevent corrosion, fouling,
formation of mud and algae.
6 Fill the plant
Do not use the unit pump
7 Execute leakage test.
8 Isolate the pipes to avoid heat dispersions and
formation of condensate.
9 Leave various point of service free (wells, vent-
holes etc).
Neglecting the washing will lead to several filter
cleaning interventions and at worst cases can
cause damages to the exchangers and the other
parts.
5 WATER CONNECTIONS

Table of Contents