M6G240F7-02 14/03/08 pag 37
APPLICATION: UNIT FOR RADIANT PANELS
SIZE 82 102 122 162 182 222 262 302
Cooling
Cooling capacity 1 kW 31,5 36,7 43,8 52,6 60,2 72,3 83,1 97,2
Comp. input power 1 kW 9,59 11,5 14 16,1 18,2 22 25,5 29,4
Total input power 2 kW 9,95 11,9 14,4 16,8 18,9 22,7 26,6 30,5
EER 1 3,16 3,09 3,05 3,13 3,18 3,18 3,13 3,19
Heating
Heat output 3 kW 29,2 33,6 38 46,9 54,1 63,3 74 85,4
Comp. input power 3 kW 6,73 7,63 8,8 10,5 12,6 14,9 17,1 20
Total input power 2 kW 7,07 8 9,1 11,2 13,3 15,6 18,2 21,1
COP 3 4,13 4,21 4,15 4,19 4,07 4,05 4,07 4,05
COMPRESSORS
Compressor type SCROLL
No. of compressors Nr 2
Capacity control steps Std Nr 3 3 2 3 3 3 3 2
Refrigerant circuits Nr 1
Refrigerant charge (C1) l 3,61 3,72 3,54 5,76 5,76 6,65 7,39 8,28
INTERNAL EXCHANGER
Type of exchanger 4 PHE
No. Of exchangers Nr 1
Water flow-rate 1 l/s 1,5 1,8 2,1 2,5 2,9 3,5 4 4,6
Max Water flow-rate l/s 1,5 1,8 2,3 2,7 3,1 4 4,6 5,4
Pressure drop kPa 48,1 47,6 41,6 42,7 43,1 37,5 39,4 41,9
Useful pump discharge head 1 kPa 91,8 80,4 72,7 42,9 17,2 111,2 102,3 82,9
EXTERNAL SECTION FANS
Fan type 5 AX
No. of fans Nr 2 2 2 4 4 4 6 6
Standard air-flow l/s 2553 2545 2514 4965 4902 4778 7196 6971
Installed unit power kW 0,17 0,17 0,17 0,18 0,18 0,18 0,18 0,18
CONNECTIONS
Water fittings 1" 1/4 2"
HYDRAULIC CIRCUIT
Max water side pressure kPa 550
Safety valve calibration kPa 600
EXPANSION VESSEL
Expansion vessel capacity l 5
Maximum water side pressure 550
No. of expansion vessels Nr 1
POWER SUPPLY
Standard power supply V 400/3/50+N
NOISE LEVELS
Sound pressure level (1 m) dB(A) 60 60 60 61 62 62 64 64
DIMENSIONS
Length mm 1703 1703 1703 1932 1932 1932 2332 2332
Depth mm 675 675 675 1100 1100 1100 1100 1100
Height mm 1209 1209 1209 1417 1417 1417 1417 1417
Packing volume m
3
1,8 1,8 1,8 4 4 4 4,5 4,5
STANDARD UNIT WEIGHTS
Shipping weight kg 325 330 380 545 565 595 690 705
Operating weight kg 315 320 370 530 550 580 675 690
(1) data referred to the following conditions :
internal exchanger water = 23/18°C
external exchanger air intake 35°C
(2) Total absorbed power is given by the compressor absorbed power
+ fan absorbed power + auxiliary circuit absorbed power.
(3) data referred to the following conditions :
outlet water internal exchanger 30/35°C
room temperature = 7°C-6°C B.U.
(4) PHE = plates
(5) AX = axial-flow fan.