M6G240F7-02 14/03/08 pag 38
APPLICATION: TERMINAL UNITS
OPERATING LIMITS (COOLING)
SIZE 82 102 122 162 182 222 262 302
EXTERNAL EXCHANGER
Max air intake temperature 1
°C 47 47 46 47 48 47 47 47
Max air intake temperature 2
°C 49 49 48 49 48 49 49 49
Min air intake temperature 3
°C
-10
INTERNAL EXCHANGER
Max air intake temperature 4
°C
22
Min. water outlet temperature 5
°C
5
Min. water outlet temperature 6
°C
-8
OPERATING LIMITS (HEATING)
SIZE 82 102 122 162 182 222 262 302
EXTERNAL EXCHANGER
Max air intake temperature (W.B.) 7
°C
22 22 24 24 24 22 24 22
Min air intake temperature (W.B.) 8
°C
-7
INTERNAL EXCHANGER
Min. water outlet temperature
°C
28
Max. water outlet temperature 9
°C
55
Warning: the still air condition is meant as absence of air flow to the unit.
Any wind condition
can let air pass through the condenser coil thus worsening the operating
limits of the unit
(see limits with air speed at 0,5 m/s & 1 m/s).
internal exchanger water = 12/7°C
ATTENTION: IN CASE OF PREDOMINANT WINDS, WINDBREAK
BARRIERS ARE NECESSARY.
Water thermal head (min / max) are indicated in the section INTERNAL
EXCHANGER PRESSURE DROP
(1) unit at full load: internal exchanger water 12/7°C
(2) internal exchanger water = 12/7°C
capacity-controlled unit (automatic capacity control)
(3) external exchanger air in quiet
(4) this limit can be exceeded for brief and transitory periods with automatic
capacity control of the unit: the maximum limit is 30°C.
(5) standard unit
outside air temperature 35°C
(6) B = Low Temperature
outside air temperature 35°C
Fluid with ethylene glycol of 40%
(7) unit at full load
outlet water internal exchanger 45°C
(8) outlet water internal exchanger 45°C
(9) room temperature = 7°C (RH = 85%)
APPLICATION: UNIT FOR RADIANT PANELS
OPERATING LIMITS (COOLING)
SIZE 82 102 122 162 182 222 262 302
EXTERNAL EXCHANGER
Max air intake temperature 1
°C
44 44 42 43 43 42 41,5 43
Max air intake temperature 2
°C
46 46 45 45 45 45 44 45
Min air intake temperature 3
°C
-10
INTERNAL EXCHANGER
Max air intake temperature 4
°C
22
Min. water outlet temperature 5
°C
5
Min. water outlet temperature 6
°C
-8
OPERATING LIMITS (HEATING)
SIZE 82 102 122 162 182 222 262 302
EXTERNAL EXCHANGER
Max air intake temperature (W.B.) 7
°C
22 22 24 24 24 22 24 22
Min air intake temperature (W.B.) 8
°C
-10
INTERNAL EXCHANGER
Min. water outlet temperature
°C
28
Max. water outlet temperature
°C
55
(1) unit at full load: internal exchanger water 12/7°C
(2) internal exchanger water = 12/7°C
capacity-controlled unit (automatic capacity control)
(3) external exchanger air in quiet
(4) this limit can be exceeded for brief and transitory periods with automatic
capacity control of the unit: the maximum limit is 30°C.
(5) standard unit
outside air temperature 35°C
(6) B = Low Temperature
outside air temperature 35°C
Fluid with ethylene glycol of 40%
(7) unit at full load
outlet water internal exchanger 45°C
(8) outlet water internal exchanger 45°C
(9) room temperature = 7°C (RH = 85%)