M08P40G16-00 WSH-XEE2 10.2-120.2 25
If there are more units connected in a local network set the mode of operation.
MODE A
Every unit manages its own compressors according to the
setpoint.
Every unit optimizes its refrigeration circuits.
Pumps always active, even with compressor stoped.
P0658 = 0
P0657 > 0 °C
setpoint1 > setpoint2 > setpoint3
or
setpoint1 < setpoint2 < setpoint3
MODE B
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Pumps always active, even with compressor stoped.
P0658 = 1
P0657 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: optimal H2O temperature control
MODE C
The master manages the single cooling.
The master optimizes individual refrigerant circuits.
Active pumps only with active compressors.
P0658 = 2
P0657 = 0 °C
setpoint1 = setpoint2 = setpoint3
plus: minimum pumps consumption need balanced system (t1 = t2 = t3)
Path: Main Menu / Unit parameters / Master Slave
Parameters Short description Description
P0655 LNinstalledUnits Number of network-connected units including the master
P0656 LNStandByUnits Number of units kept in standby
P0657 LNOset
Temperature Oset the master sum or subtract, depending on the way you set, in order of priority, to the set point of
the slave
P0658 TypeRegMS Operation mode: 0=mode A; 1=mode B; 2=mode C
P0659 LNAddress ProcessBus address unit