4.5.1 Isolate devices (by device)
This function is used to isolate and de-isolate individual devices.
Step to follow
1. Go to the top level maintenance menu as described in section 4.1
MAINTENANCE MORE
^
1. Edit disabled 4. Reports to display
2. View disabled 5. Reports to printer
3. Enable all 6. Calibrate detectors
2. Press 1
MAINTENANCE: EDIT DISABLED
1. Point 4. Sounders
2. Zone 5. Outputs
3. Extinguishing system 6. Remote Alarm
3. Press 1
MAINTENANCE: EDIT DISABLED: POINT
Enter point address : 1001
4. Enter the four digit address for the device to be isolated. Alternatively use the MORE or
up/down arrow keys to select the required address and press .
MAINTENANCE: EDIT DISABLED: POINT
Point: 1001 (Enabled )
1. Disable
2. Enable
5. Press 1 to select disable or 2 enable a previously isolated device
MAINTENANCE: EDIT DISABLED: POINT
Point: 1001 (Disabled )
1. Disable
2. Enable