6. Press HOME to exit the menu. If further devices are to be disabled/enabled then use the
up/down arrows to select another device or press the ESC key and enter the four digit address
number of the next device to be disabled.
Saving…
The menus are exited and the device isolation status is saved. If any fire devices are currently
isolated then the yellow disabled-point LED will show on the panel front together with the
common disabled LED.
The disabled events are also printed out on a built in printer if one is present and enabled.
Note that once a device is disabled by day, it will switch between disabled and enabled states
with the panel day and night operation status.
4.5.2 Isolate devices (by zone)
This function is used to assign the same isolation status to all devices in a zone.
Step to follow
1. Go to the top level maintenance menu as described in section 4.1
MAINTENANCE MORE
^
1. Edit disabled 4. Reports to display
2. View disabled 5. Reports to printer
3. Enable all 6. Calibrate detectors
2. Press 1
MAINTENANCE: EDIT DISABLED
1. Point 4. Sounders
2. Zone 5. Outputs
3. Extinguishing system 6. Remote Alarm
3. Press 2
MAINTENANCE: EDIT DISABLED: ZONE
Enter zone number : 001
http://www.firealarmengineers.com