Clymac ZP3 - Page 22

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4. Enter the three digit address for the zone to be isolated. Alternatively use the MORE or
up/down arrow keys to select the required zone number and press .
MAINTENANCE: EDIT DISABLED: ZONE
Zone: 001 = (Enabled ) > info
1. Disable
2. Enable
5. Press 1 to select disable or 2 to enable a previously isolated device
MAINTENANCE: EDIT DISABLED: ZONE
Zone: 001 = (Disabled ) > info
1. Disable
2. Enable
6. Press HOME to exit the menu. If further devices are to be disabled/enabled then use the
up/down arrows to select another device or press the ESC key and enter the four digit address
number of the next device to be disabled.
Saving…
The menus are exited and the device isolation status is saved. If any fire devices are currently
isolated then the yellow disabled-point LED will show on the panel front together with the
common disabled LED.
The disabled events are also printed out on a built in printer if one is present and enabled. The
events should be accepted and the panel reset when the devices are enabled.
Note that once a device is disabled by day, it will switch between disabled and enabled states
with the panel day and night operation status.
http://www.firealarmengineers.com