EasyManuals Logo

CMC Airmaster R1 User Manual

Default Icon
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
C.M.C. n.v. - Airmaster R1 installation guide – base unit – V1.1 – MANY0317A.00
Page 9 of 41
3.3 Resistance to vibration and shock
operating
IEC 68-2-6 Fc Vibrating, 10-150Hz, 2g, 10sweeps/axis
not operating (storage and handling)
IEC 68-2-6 Fc Vibrating, 10-150Hz, 1g, 5sweeps/axis
IEC 68-2-27 Ea Shock, 15g, 11ms, 3 shocks/axis
IEC 68-2-29 Bump, 10g, 6ms, 500 bumps / axis
3.4 Protection degree
The protection degree is IP00.
The R1 unit must be mounted within an enclosure or housing
with suitable protection rating.
4. Safety
The Airmaster R1 is a class I equipment in which protection against electric shock does not
rely on basic insulation only, but which includes an additional safety precaution in that
accessible conductive parts are connected to the protective earthing conductor in the fixed
wiring of the installation in such a way that they cannot become live in the event of a failure
of the basic insulation.
The Airmaster R1 base unit must be earthed. See drawing below (indicated with the
yellow/green wire)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CMC Airmaster R1 and is the answer not in the manual?

CMC Airmaster R1 Specifications

General IconGeneral
BrandCMC
ModelAirmaster R1
CategoryController
LanguageEnglish

Related product manuals