3 Specification
3.1 Technical data:
Optional
CO NO NO
2
Measurement principle:
Electrochemical Cell
Measurement units:
ppm
ppm
ppb
Nominal measurement range
(typical):
0 to 800 ppm
0 to 160 ppm
0 to 10 ppm
Measurement range (typical):
1 to 300 ppm
1 to 30 ppm
1 to 5 ppm
Accuracy:
±2 ppm
±2 ppm
±100 ppb
Resolution:
0.1 ppm
0.1 ppm
1 ppb
Response time:
30 seconds
Averaging time:
30 seconds to 3 minutes (Configurable)
Path length:
N/A
Operating temperature:
+5°C to +50°C (Cell temp)
Humidity:
10-90% R.H
Storage temp:
+5°C to +25°C
Nominal power supply:
24V DC
Nominal power consumption:
30W
Interface:
16x2 Display + Keypad
Temperature sensor:
On board (PCB)