CODEL Operation and Maintenance Manual
Issue : A Rev. : 3 Date : 13/11/2018 Ref. : 100351
P a g e | 35
Standard baud rate - 4800
Bits per byte - 1 start bit
- 8 data bits (least significant sent first)
- 1 stop bit
- no parity
The MODBUS output from the TT AQM is at 4800 baud format: 1 start bit, 8 data bits, no parity, 1 stop bit.
The MODBUS output from the TT AQM will be connected via RS485.
The TT AQM comms is Standard Modbus protocol with RTU framing and only function code 03 is supported.
The TT AQM will be a MODBUS slave device.