IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
If this setpoint is in ENABLED position the display backlight is temporarily 
switched off during gen-set start. 
 
Setpoint: FastHistPeriod 
100 ms, 300 ms, 500 ms, 1 s, 3 s [-] 
This setpoint adjusts the period with which fast history records are written. Fast 
history is triggered if level 2 alarm (for more information on alarm levels please 
refer to this section) is issued and the engine is running (at least one condition 
from this list is fullfiled). For any setting of this setpoint Fast History contains 50 
records.  
 
Setpoint: ConvCoefPulse1 
This setpoint adjusts the rate of increasing of the PulseCounter #1 module. The 
module counts pulses at the input PulseCounter 1 and if the input pulses counter 
reaches value given by this setpoint, the counter value PulseCounter 1 (in the 
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both 
counter value and input pulses counter are stored in the nonvolatile memory. 
 
Setpoint: ConvCoefPulse2 
This setpoint adjusts the rate of increasing of the PulseCounter #2 module. The 
module counts pulses at the input PulseCounter 2 and if the input pulses counter 
reaches value given by this setpoint, the counter value PulseCounter 2 (in the 
group Statistic) is increased by 1 and input pulses counter is reset to 0. Both 
counter value and input pulses counter are stored in the nonvolatile memory. 
 
Setpoint: ConvCoefPulse3