IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
 
Setpoint: ForceBlockDel2 
This setpoint adjusts the delay after the binary input Force block 2 has been 
deactivated, when the alarms configured as Force block #2 are started to be 
evaluated. 
 
Setpoint: ForceBlockDel3 
This setpoint adjusts the delay after the binary input Force block 3 has been 
deactivated, when the alarms configured as Force block #3 are started to be 
evaluated. 
 
Setpoint: ResetActAlarms 
Pressing of the fault reset button (at any terminal or external 
button) resets only inactive alarms. Active alarms remain in 
the alarmlist unchanged and must be reset again when they 
become inactive.  
Pressing of the fault reset button (at any terminal or external 
button) resets all alarms that are currently present in the alarm 
list. Inactive alarms disappear from the alarm list immediately, 
active alarms are changed to "confirmed" state and disappear 
when the alarm condition disappear or the alarm starts to be 
blocked.  
 
NOTE:  
ENABLED position corresponds to the method how the IG-classic and IS-classic 
controllers handled the alarms.  
 
 
Setpoint: Overspeed