Shows the text EmergMan in the engine status on the main screen.  
  Stops all functions regarding the gen-set control, deactivates all outputs 
related to it. The complete list of effected logical binary outputs is at the 
bottom.  
  Stop Fail alarm is not beeing evaluated and stop solenoid is not activated 
if nonzero speed is detected.  
  Voltage, current, power and other electric measurements are active. 
  When the input is deactivated, the controller takes control over the gen-
set according to the situation in which the gen-set was in the moment of 
deactivation. I.e. the gen-set remains running loaded if it was running and 
GCB was closed in the moment the input was deactivated.  
 
NOTE:  
For successful recovery from a running state when the input is deactivated it is 
recommended to use pulse-type control outputs instead of continous-type. E.g. 
Stop Solenoid for fuel supply control and GCB ON coil, GCB OFF coil for breaker 
control.  
 
Logical Binary Outputs that are deactivated (directly or indirectly) when Emerg. 
manual is active:  
Starter  
Fuel solenoid  
Prestart  
Cooling pump  
CB close/open (GCB and MCB)  
CB ON coil (GCB and MCB)  
CB OFF coil (GCB and MCB)  
CB UV coil (GCB and MCB)  
Stop solenoid  
Stop pulse  
Speed up  
Speed dn  
AVR up  
AVR dn  
Ignition  
Ventilation  
Idle/Nominal  
Prelubr pump  
In synchronism 
ECU PwrRelay  
Ready for load  
Stand-by ready  
Operational  
Ready  
Not Ready  
CranckProcedure  
Starting  
Idle run  
Running  
ForwardSynchro  
ReverseSynchro  
Warming  
Soft load  
Loaded  
Soft unld  
Cooling