Repeated CB close command:
2s
2s
1s
BO: CB OFF coil
2s
BO: CB status
BI: CB fdb neg
BI: CB fdb
BO: CB ON coil
1s
BO: CB close/open
BO: CB UV coil
If the CB is not closed after
the first attempt, it is only reset
by OFF pulse and no CB fail is
issued. This would be issued
after the second unsuccessfull
attempt.
BO: CB status = 0
BI: CB fdb neg = 1
BI: CB fdb = 0
BO: CB fail
ON pulse has finished and CB
status is not =1. CB fail is
issued immediatelly