EasyManua.ls Logo

ComAp IM-NTC-BB - Setpoints; Password Protection; Table of Setpoints

ComAp IM-NTC-BB
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IGS-NT Installation Guide
99
• Input output address is displayed on the front panel LED’s
• Use PC configuration tool to configure controller according external modules setting
IS-BIN16/8 module has two separate CAN1 addresses for binary inputs Group 1, Group 2 and
binary outputs Group (total three addresses). The CAN1 address for BI Group 1 and for BO
Group 2 can be adjusted on the IS-BIN16/8. The address for BI Group 2 is set automatically
to the address following BI Group 1.
HINT
If part of IS-BIN16/8 is not required for use, CAN address 0 disables corresponding CAN
message (group data are not send).
11.2.1. IS-AIN8, IS-BIN8/16 address setting
• Press Address button during IS-AIN8 power supply on to switch to addressing mode.
• Then repeatedly press or keep pressed address button to adjust required address
according to controller configuration.
• After setting requested address, release the buttons and wait until the digits blink – it
indicates write the changed address to EEPROM memory.
11.2.2. IS-AIN8, IS-BIN8/16 SW version check
Let suppose IS-AIN8 of SW version 1.4 for this example. Shortly press address button.
Following sequence appears on the display: number “1”, one second pause, number “4”, two
second pause, number “1”, one second pause, number “4”, two second pause and finally IS-
AIN8 actual address.
11.2.3. Example of Wiring
Controller 1
CAN 2CAN 1
L
COM
H
H
L
H
L
COM
COM
IS-AIN8_1
CAN 1
IS-AIN8_8
CAN 1
Addr.:1
Addr.:1
Controller 2
CAN 2CAN 1
Addr.:2
L
COM
H
L
COM
H
Addr.:8
H
L
H
L
COM
COM
IS-BIN16/8_1
CAN 1
IS-BIN16/8_6
CAN 1
Addr.: in1 Addr.:12
120 Ω
out1 out6
CAUTION!
CAN bus line has to be terminated by 120 ohm resistors on the both ends.

Table of Contents