InteliLite
NT
AMF20/25, SW version 2.2, ©ComAp September 2014 63
IL-NT-AMF-2.2-Reference Guide.pdf
alarm is not active and
FAULT RESET is pressed
AL AI1 Wrn
Output closes if the engine oil pressure (configured to the first analog input) warning alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI2 Sd
Output closes if the engine water temperature (configured to the second analog input) shutdown alarm
activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI2 Wrn
Output closes if the engine water temperature (configured to the second analog input) warning alarm
activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
AL AI3 Sd
Output closes if the engine Fuel Level (configured to the third analog input) shutdown alarm activates.
AL AI3 Wrn
Output closes if the engine Fuel Level (configured to the third analog input) warning alarm activates.
BI1..7 Status
* IOM BI1..7 Status
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if
alarm is not active and
FAULT RESET is pressed
In case the assigned binary input is configured to any control function, the output propagates the state
of the input.
* AL IOM AI1..4 Wrn
Output closes if warning alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
* AL IOM AI1..4 Sd
Output closes if shutdown alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
* ExtBI1..7 Status
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp intelilite nt amf20 and is the answer not in the manual?

ComAp intelilite nt amf20 Specifications

General IconGeneral
BrandComAp
Modelintelilite nt amf20
CategoryController
LanguageEnglish

Related product manuals