InteliNano-NT Plus, SW version 1.5, ©ComAp October 2013 2
InteliNano-NT-Plus-1.5-Fast User Guide.pdf
Setpoints
Use and buttons to move or change value. Start button to select setpoint or confirm changes and Stop button to go back.
Basic settings
Setpoint
code
Setpoint name
B01
Nominal Voltage Ph-N
80 480 V
B02
Nominal Voltage Ph-Ph
80 600 V
B03
Nominal Frequency
50 Hz (1), 60 Hz (2)
B04
Connection Type
Mono Phase (1), SplitPhase (2),
3Ph3Wire (3), 3Ph4Wire (4)
B05
Units Format
Metric unit format (1), US unit
format (2)
B06
AMF Function
Disable (1), Enable (2)
B07
Zero Power Mode Delay
0-360 min
B08
Light Tower Mode
Disable (1), Enable (2)
B09
Nominal Current
1 1000 A
B10
CT Ratio
1 5000 A
B11
Nominal RPM
100-4000
´
Generator protections
Setpoint
code
Setpoint name
G01
Generator Overvoltage Shutdown
G02 200 %
G02
Generator Undervoltage Shutdown
0 - G01 %
G03
Generator Overfrequency Shutdown
G04 130 %
G04
Generator Underfrequency Shutdown
0 G03 %
G05
Generator Short Circuit Shutdown
100 500 %
G06
Generator Short Circuit Delay
0 10,00 s
Engine parameters and protections
Setpoint
code
Setpoint name
E01
Prestart Time
0-600 s
E02
Maximum Cranking Time
0-60 s
E03
Cooling Time
0-3600 s
E04
Oil Pressure Shutdown
0-10 Bar
E05
Coolant Temperature Shutdown
0 -150 °C
E06
Battery Undervoltage
8 40 V
E07
Warning Maintenance
0 10000 h
E08
Oil Pressure Starter Disengagement
Disable (1), Enable (2)
E09
Choke Time
0 3600 s
E10
Minimal Stabilization Time
1 300 s
E15
Fuel Level Shutdown
0 20%
AMF(Auto Mains Failure) settings
Setpoint
code
Setpoint name
A01
Emergency Start Delay
0 600 s
A02
Mains Return Delay
1 3600 s
A03
Mains Overvoltage
A04 150 %
A04
Mains Undervoltage
50 A03
A05
Mains Overfrequency
A06 150 %
A06
Mains Underfrequency
50 A05 %
To apply all changes return to the main setup menu and restart the controller by pressing the Stop button.
Alarms and Events
Events
Mains Return
Mains Fail
Manual Start
Remote Start
AMF Start
Manual Stop
Remote Stop
AMF Stop
Auto On
Auto Off
Power On
Island Operation
Warnings
Warning Maintenance
Low Battery
Low Fuel Level
External Warning 1
External Warning 2
External Warning 3
ECU Communication Error
MCB Fail
Mains CCW Rotation
Shutdowns
Emergency Stop
Overspeed
Underspeed
Low Oil Pressure
High Coolant temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
Voltage Autodetect
Generator Short Circuit
Fuel Level SD
ECU
For ECU configuration use PC software NanoEdit. For more details see InteliNano AMF Reference Guide.
Technical data
Power supply range
6-36 VDC
Power supply drop-out immunity
100 ms
Power consumption
35 295 mA
Zero Power Mode consumption
52 - 344 µA
Binary outputs (up to 6)
Low current outputs (4)
500 mA
High current output (2)
6 A (long term) / 10 A (short term) (L≤500mH)
Total output current
10 A (long term) / 16 A (short term) (L≤500mH)
Analog inputs (up to 3)
Galvanic insulation
Not insulated
Electrical range
0 - 2500
Resolution
0,1 Ώ
Precision
2 % ± 3 Ώ
Charging alternator preexcitation circuit
Excitation current
100 mA
Charging fail threshold
80 %
Operating temperature
-20... 70 °C
Operating humidity
95 % non-condensing (IEC/EN 60068-2-30)
Protection degree (front panel)
IP65 with GASKET 4x405 only
IP50 without gasket
Storage temperature
-30... 80 °C
Binary inputs (up to 6)
Input resistance
1,5 kΏ
Closed contact voltage
<2 V
Open contact voltage
>3,5 V
Generator/Mains measurements
Measurement input
1ph gen. voltage,1ph current, 3ph mains voltage
1ph
current
Measurement type
True RMS
Voltage range
480 V Ph-Ph (277 V Ph-N)
Max. measured voltage
340 V Ph-N
Voltage accuracy
1 %
Frequency range
40 70 Hz
Frequency accuracy
1 %
Current range
0 - 5 A
Current accuracy
2% True RMS

Other manuals for ComAp InteliNano NT Plus

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliNano NT Plus and is the answer not in the manual?

ComAp InteliNano NT Plus Specifications

General IconGeneral
BrandComAp
ModelInteliNano NT Plus
CategoryController
LanguageEnglish

Related product manuals