IGS-NT Communication Guide
67
ModBus (not available at USB port of I-LB+, USB port always works in ComAp mode)
Direct/Modem selects between direct connection (via RS232 or RS485) and modem connection type
DIRECT
RS232/RS485 selection of serial communication type
ADR1/ADR2 selection between two available local communication channels; if I-LB+ is used,
the USB communication automatically occupies the other channel
MODEM
ADR1/ADR2 selection between two available modem communication channels; IG/IS-NT
controllers only, in ID the secondary modem channel not available
Setting HW/SW control has no influence; a modem with HW control is always expected in this
mode
ModBus Rate (9600 / 19200 / 38400 / 57600 bps) selects the communication speed when ModBus
protocol is selected, no matter if in Direct or Modem mode
Note: For more information read IGS-NT accessory modules manual.
5.3 I-CR Module for CAN Bus Extension
If the distance between units is too high to fit into the 200 m limit (or 900 m for 8 controllers), CAN repeater
module (I-CR) can be used to extend it.
Typical case in line extension:
Connection of I-LB, combination of different CAN bus speeds:
This connection allows PC communication to all controllers in the system (e.g. via InteliMonitor), including a
distant InteliMains unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliSys NTC BaseBox and is the answer not in the manual?

ComAp InteliSys NTC BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliSys NTC BaseBox
CategoryController
LanguageEnglish

Related product manuals