IS-NT-Async-SPI, SW Version 1.2, ©ComAp – February 2011
IS-NT-Async-SPI-1.2.PDF
85
Date/Time
Time stamp act [ DISABLED / ENGINE RUNNING / ALWAYS ] (FV)
Defines the activity of time stamp function:
DISABLED No periodic records are made.
ENGINE RUNNING Records are made with period given by Time stamp per only if engine is running.
ALWAYS Records are made with period given by Time stamp per regardless of the engine state.
Force value possibility: Yes
Time stamp per
Time interval for periodic history records.
Step: 1 min
Range: 1 - 240 min
#SummerTimeMd [ DISABLED / WINTER / SUMMER,
WINTER-S, SUMMER-S ]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER
(SUMMER) : Automatic switching between summer and wintertime is enabled and it is set to
winter (summer) season.
WINTER-S
(SUMMER-S) : Modification for southern hemisphere.
#Time [HHMMSS]
Real time clock adjustment.
#Date [DDMMYYYY]
Actual date adjustment.
Hint
:
#Time and #Date setpoints are synchronized via CAN bus each hour with the lowest address controller.
#Time or #Date change in any controller changes Time or Date in all controllers on CAN bus.