Commands Reference
CoolMaster PRM
10
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
DESCRIPTION
Turn on all indoor units.
EXAMPLE
>allon
OK
EXIT CODE
OK
Request Successfully Executed
4.1.3 boot
SYNOPSIS
boot
DESCRIPTION
Switch CoolMaster to bootloader mode. Bootloader mode is used for Firmware Update. For details
please see the Firmware Update section.
EXAMPLE
>boot
reboot...
4.1.4 cool
SYNOPSIS
cool <UID>
DESCRIPTION
Set indoor unit UID mode to COOL.
EXAMPLE
>cool 102
OK
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
4.1.5 dry
SYNOPSIS
dry <UID>