Commands Reference
CoolMaster PRM
25
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
l - Low Fan
P
P
P
L - Low Fan with Fresh-Up
P
h - High Fan
P
P
P
H - high Fan with Fresh-Up
P
s - Super High Fan
P
P
A - Auto Fan
P
P
On/off control for VAM units is performed with regular on off commands.
EXAMPLE
>vam 101 a
OK
VAM unit 101 auto mode
>vam 101 L
OK
VAM unit 101 low fan speed with fresh-up
>vam 101 h
OK
VAM unit 101 high fan speed
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
v 2.4.7
CoolMaster 4000M
v 2.8.4
CoolMaster 6000L
v 2.8.0
4.1.23 lock
SYNOPSIS
lock <UID>
lock <UID> +
lock <UID> -
lock <UID> [+|-][o|m|s] ...
DESCRIPTION
This command controls Locking (Prohibit) of the Wall Controller (Thermostat) operation for unit <UID>.
Following operations can be Locked/UnLocked:
o - On/Off
m - Mode change
s - Set Temperature change
n - On (CoolMaster 1000D Only)
· lock <UID>
Query current Lock settings
· lock <UID> +
Lock ALL
· lock <UID> -
UnLock ALL
· lock <UID> <+|-><o|m|t> ...