Commands Reference
CoolMaster PRM
13
www.coolautomation.com
© 2015 Cool Automation LTD
Rev 4.08
CoolMaster 3000T
any
CoolMaster 4000M
any
CoolMaster 6000L
N.A.
CoolMaster 7000F
N.A.
CoolMaster 8000I(MH)
any
CoolMaster 9000H
N.A.
CoolMaster G
N.A.
4.1.10 fspeed
SYNOPSIS
fspeed <UID> <l|m|h|a|t>
DESCRIPTION
Set indoor unit UID fan speed to low, medium, high, auto, top.
EXAMPLE
>fspeed 101 l
OK
Set unit 1-01 fan speed to low
>fspeed 101 m
OK
Set unit 1-01 fan speed to medium
>fspeed 101 h
OK
Set unit 1-01 fan speed to high
>fspeed 101 a
OK
Set unit 1-01 fan speed to auto
>fspeed 101 t
OK
Set unit 1-01 fan speed to top
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
any
Supported: l h
2.5.1
Supported: l m h
CoolMaster 2000S
any
Supported: l m h a
CoolMaster 3000T
any
Supported: l m h a
CoolMaster 4000M
any
Supported: l m h a t
CoolMaster 6000L
any
Supported: l m h a t
CoolMaster 7000F
any
Supported: l m h a
CoolMaster 8000I(MH)
any
Supported: l m h t
CoolMaster 9000H
any
Supported: l m h
CoolMaster G
any
Supported: l m h a
4.1.11 off
SYNOPSIS
off <UID>
DESCRIPTION
Turn off indoor unit UID.
EXAMPLE