EasyManuals Logo

Coopra 40C Installation Manual

Default Icon
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Coopra Advanced Heating Technologies Installation manual E40C
5
Status Reading
1.3.1. Normal state (continuous code)
P
With initialisation and after restoration of supply power de-aeration programme runs for 2 minutes.
The boiler pump and 3-way valve (if applicable) switch several times, with the purpose to move
eventual air out of the boiler; burner off
0
Stand-by (no heat demand)
C
Heating heat demand, temperature above setpoint, burner off
C.
Heating heat demand, temperature below setpoint, burner on
J
Heating heat demand, 3 minutes anti-cycling time, burner off
c
Pump after run heating mode, burner off
d
DHW heat demand, temperature return sensor of Combi-boiler above setpoint, burner off
d.
DHW heat demand, temperature return sensor of Combi-boiler below setpoint, burner on
b
HWS heat demand, temperature external cylinder above setpoint, burner off
b.
HWS heat demand, temperature external cylinder below setpoint, burner on
o
Frost protection 8°C; burner off, pump on
o.
Frost protection 3°C; burner on, pump on
C
flashing
Chimney sweeper function (ionisation current on the right hand segments)
Status Reading
1.3.2. Blocking state (continuous code)
2
Return sensor temperature 5°C above flow sensor temperature, pump on, burner off
6
Combi boiler internal tank sensor not connected or open (parameter H=01)
6.
Combi boiler internal tank sensor shortcut fault (parameter H=01)
9
Flow or return sensor temperature > 95°C
A
Flue gas sensor temperature > 100°C
b/r
Hot water on right unit of TWIN boiler
E
No SLAVE connected / PCB is set as MASTER, (parameter A=0)
SLA/01
No MASTER connected / PCB is set as SLAVE, (parameter A=1)
P
Water pressure low or high, display shows ‘P’+ pressure
t
Outdoor sensor summer switch on, burner off, (parameter O/t)
Status Reading
1.3.3. Lock-out state (flashing code)
1
Max delta temperature, differential temperature between flow and return sensor limits 50°C
1
Boiler does not pass temperature test. After burner start the flow sensor must rise 3°C more in
temperature than return sensor within 20 seconds (after 3 start attempts follows lock-out)
2
Flame signal lost 3 times during operation
5
Fan speed error (fan speed deviates > 30% from the speed setpoint)
8
Flame signal detected with closed gas valve
9
Eeprom programmed (to reset press the Set/Reset button)
A
Flue gas temperature > 100°C for more then 3 times within 30 minutes
E
Internal regulation fault / A/D conversion fault (depending type of error display shows ‘E’ or “EEE”)
E t1
Flow sensor open or shortcut fault
E t2
Return sensor open or shortcut fault
E t3
Flue gas sensor open or shortcut fault
F
Too many (4 times) consecutive start attempts
H
Flow or return sensor temperature > 105°C
O
Safety limiter contact is open (no limiter on this boiler, contacts bridged)

Table of Contents

Other manuals for Coopra 40C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Coopra 40C and is the answer not in the manual?

Coopra 40C Specifications

General IconGeneral
BrandCoopra
Model40C
CategoryBoiler
LanguageEnglish

Related product manuals