Cornelius IAC322 - Troubleshooting: Cuber Stuck in Freeze Cycle

Cornelius IAC322
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60TD 204
Trouble RemedyProbable Cause
COMPRESSOR
RUNS BUT
DOES NOT
COOL, CIRCUIT
BOARD
INDICATOR
LIGHTS ON
A. Low charge. A. Leak check
Recharge.
B. Hot gas
solenoid
leaking.
B. Replace.
C. Defective
expansion
valve.
C. Replace.
D. Inefficient
compressor.
D. Replace.
E. Internal
by-pass
open,
compressor
noisy.
E. Permit pressures
to equalize.
CUBER
REMAINS IN
THE FREEZE
CYCLE
A. Check
suction line
thermistor
(sensor)
lead wire
connection
at the circuit
board.
A. Tighten,
reattach.
B. Evaporator
thermistor
shorted.
B. Replace.
C. Check
thermistor
(1K ohm).
C. Replace if out of
range.
D. Ice bridge
setting too
low.
D. Adjust per bridge
adjustment
instructions.