EasyManua.ls Logo

Coster YHC 700 - Page 20

Coster YHC 700
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. YHC Configuration YHC 700
7.2.1.1 YLC configuration
You can use this page to specify:
How many controllers are connected to YHC700 (up to 20). Default: 0
The communication protocol used for data exchange with these controllers. Default:
ModBus/RTU
If the YHC function of data exchange between controllers is enabled or not. Default:
Disabled
If alarm reading is enabled or not. Default: Disabled
Whether the YLC data caching is enabled or not. Default: Disabled
For each controller, you can specify:
Whether it is enabled or not (this can be useful in the support phase, to
isolate any source of errors)
The connection mode (RS485 bus or Ethernet
5
). Default: RS 485
The Modbus address (Default: 1)
The IP address, if any (if the specified connection mode is Ethernet).
o Whether the instantaneous data logger cloud sending is enabled on that
controller. Default: No
A short description (used in the diagnostic web pages)
NOTE: Modbus address and communication protocol must be the same as those set on YLC;
The selected communication protocol must necessarily be used also for ClimaOffice
connections (YHC does not perform protocol conversions)
5
Used to support the existing installations where YLC is connected to STE000.
20

Table of Contents