1-9. Read Holding Registers
FUNC
CODE
Starting
Address
Description
number of
word to
read
CMD AND RESPONSE
Value
3
0X0001
Read the Setting
output
voltage(SV?)
1
A0 03 00 01 00 01 CC BB
A0 03 00 01 04 B0 0E 0F
0x04B0 =1200
12.00 V
0X0002
Read the Setting
output current
(SI?)
1
A0 03 00 02 00 01 3C BB
A0 03 02 17 70 0B 89
0X1770 = 6000
For model
12~57V,its
60.00A.
For model
120V~400V
model, its
6.000A
0X0004
Read master or
slave id(ID?)
1
A0 03 00 04 00 01 DC BA
A0 03 00 04 00 00 1D 7A
0X0000 = 0
0X0006
Read Modbus ID
1
A0 03 00 06 00 01 7D 7A
A0 03 00 06 00 00 BC BA
0X0000 = 0
0X0007
Read PMBUS ID
1
A0 03 00 07 00 01 2C BA
A0 03 02 00 50 05 A1
0X01~0X7F
(Default 0x50)
0X0008
Read POWER
SOFTSTART
1
A0 03 00 08 00 01 1C B9
A0 03 02 00 19 C4 57
0X0009
Read SV
SOFTSTART
1
A0 03 00 09 00 01 4D 79
A0 03 02 00 06 85 9F
ramp up time 0
to 100% volt in
millisecond