Loading...
10
Increasing S500 DC cable size helps improve the situation.
COTEK recommends the following cables for optimum inverter
performance. (Apply both 110V and 220V versions)
Model
Wire AWG
Inline fuse
S500-112
# 8
ʁ125A
S500-124
# 10
ʁ80A
S500-212
# 8
ʁ125A
S500-224
# 10
ʁ80A
NOTE
Batteries are capable of providing very large currents in case of
short circuit. The fuse should be as close to the positive battery
terminal as possible. Use Bussmann ANN series fuses (will also
require Fuse Block 4164) or equivalent.
3-5. Installation
Before connecting your applications to the inverter, always check the
power draw of your appliances. The inverter can supply surge power for
a short time so as to start up electrical equipment such as motors and
pumps which need more power while starting up.
When all the above requirements are satisfied and all connections are
made, it’s time to turn on the inverter by switching the power to ‘ I ’
position. The sine wave filters provide sine wave output voltage when
driven from the AC outlet.
To save the battery power, you are highly recommended to turn off the
inverter when it is not being used.
DC input voltage status as follows
Model
DC Input Over
Voltage
DC Input Under
Voltage
Shut-down
Restart
Shut-down
Restart
S150/S300 12V
models
15.3VDC
14.8VDC
10.5VDC
12.5VDC
S150/S300 24V
models
30.6VDC
29.6VDC
21.0VDC
25.0VDC
S500 12V models
16.0VDC
14.5VDC
10.5VDC
12.5VDC
S500 24V models
32.0VDC
29.0VDC
21.0VDC
25.0VDC