COTES C35 OPERATING AND SERVICE HANDBOOK page 10/71
Configuration-C
In addition to the Configuration-B features, the Configuration-C provides:
Control of process air fan, making installation easier
Monitoring and control of air flows [m
3
/hour]
Energy-saving program, for situations where energy consumption is the prime consideration
Low-noise program, for situations where silence is the prime consideration
CUSTOM program, for situation where dehumidifier parameters needs to be controlled
Configuration-D
In addition to the Configuration-C features, the Configuration-D provides:
Accurate control of humidity level, whether % relative humidity or specific humidity [g/kg]
Continuous measurement of capacity
Detailed energy-saving program, for situations where energy consumption is the prime
consideration
Intended use of dehumidifier
The dehumidifier is designed for dehumidifying/conditioning atmospheric air only filtered with at
least a G4 filter. Unless specifically stated in the manual or in a separate agreement with Cotes or a
Cotes dealer, this dehumidifier must not be used for the following purposes:
Conditioning gases other than atmospheric air at ambient pressure
Conditioning air contaminated with any chemical or other aggressive/corrosive elements
including salt (sodium chloride)
Conditioning explosive or flammable air including using the dehumidifier in ATEX-
classified zones.
The unit is intended for use in residential, commercial and industrial environments.
Operating conditions standard models (E and D)
For the process and regeneration air inlet, the following operating conditions must be respected:
Relative humidity 0100%
Temperature 0–40°C
Pressure Ambient ± 100 Pa
It is only possible to deviate from these ranges if such deviations were specifically mentioned when
the order was placed, and special considerations have been incorporated into the unit in order to deal
with this.
Depending on configuration the actual sensor range may be limited to 5-100 %.