Product Manual Doc. 9341A GLS-ODT-C-CN and GLS-ODT-C-NS 7
Connections
5-pin 3.5mm detachable terminal block;
16 AWG maximum wire width supported, includes the following terminals
(1) Crestron secondary port:
+24V DC power input
OCC Occupancy sensor control signal output;
Provides 24VDC high logic signal when occupancy is detected (both PIR and US
must sense occupancy to provide 24V signal if room is transitioning from a
vacant to occupied state;
After initial occupancy is detected, either PIR or US detection will trigger the
24V signal to maintain the occupied state);
Short circuit protected;
Connects to a GLS-SIM Integration Module (sold separately) on any Crestron®
control system
NC Unused
G Ground
IR IR single direction, transmits information read from remote by IR receiver on
sensor
Power Requirements
Current Consumption 60mA @ 24VDC
Cresnet Power Usage 1.5 W
Environmental
Temperature 32° to 104°F (0° to 40°C)
Humidity 10% to 90% RH (noncondensing)
Construction
Housing Plastic, white
Mounting Mounts to a 4in. (102mm) octagon box or 3-1/2in. (88mm) diameter hole
created by provided cutout template;
Includes mounting screws and integral toggle clamps;
A 1-1/2in. (38mm) minimum mounting depth is recommended
Dimensions
Diameter 4.80in. (122mm)
Depth 2.29in. (58mm) overall;
Projects 0.97in. (25mm) from the surface when installed
Weight
0.7lb (309g)