Menu system overview Crowcon Gasmaster
26
Menu Item Values Description Codes
(as shown on display)
Warnings menu (lists warnings present on the system)
No warnings (end of list) No warnings are present.
Warnings Supervisor mode System configurations may be changed. 1
Global inhibit All input channels are inhibited. 2
Testing audio visual alarm Audible visual outputs will be driven. 3
Service/calibration due Service or calibration interval has expired. 4
Common relay forced Common alarm or fault relays are being forced 5, 6, 7
to their 'alarm' state.
Main Supply Fail Main supply has failed and the system is 8
running on batteries
Detector #1 stabilising Detector is currently in its stabilisation or reset 9, 17, 25, 33
period*, (see page 30).
Detector #1 input low Detector input signal is between 1 and 3 mA.* 10, 18, 26, 3
Only applies when the 'Interpret 2 mA'
command is set to Warning in the channel
configuration.
Detector #1 initiated A 2 mA inhibit signal has been received from a 11, 19, 27, 35
inhibit detector.* Only applies when the 'Interpret
2 mA' command is set to Inhibit in the
channel configuration.
Chan #1 inhibited Input channel is in an inhibit state* . 12, 20, 28, 36
Chan #1 input simulated Channel input is being forced in Test mode.* 13, 21, 29, 37
Chan #1 output forced Channel analogue output is being forced in 14, 28, 30, 38
Test mode.*
Chan #1 relay forced Channel alarm relay is being forced in 15, 16, 23, 24
Test mode.* 31, 32, 39, 40
Chan#1 pellistor saver Pellistor saver mode has been disabled, the 41,42,43,44
disabled sensor may be damaged if exposed to gas
concentrations above 100%LEL.
* #1 denotes the channel number and therefore may read #2, #3 or #4 on Gasmaster.