14
02
Maximum charging
current: To configure
total charging current
for solar and utility
chargers.
(Max. charging current
= utility charging
current + solar charging
current)
50A
60A
03 AC input voltage range
Appliances (default)
If selected, acceptable AC input voltage
range will be within 90-280VAC.
UPS
If selected, acceptable AC input voltage
range will be within 170-280VAC.
05 Battery type
AGM (default)
Flooded
User-Defined
If User-Definedis selected, battery
charge voltage and low DC cut-off
voltage can be set up in program 26, 27
and 29.
06
Auto restart when
overload occurs
Restart disable
(default)
Restart enable
07
Auto restart when over
temperature occurs
Restart disable
(default)
Restart enable
09 Output frequency
50Hz (default)
60Hz
11
Maximum utility
charging current
Note: If setting value in
program 02 is smaller
than that in program in
11, the inverter will
apply charging current
from program 02 for
utility charger.
15A
25A (default)
12
Setting voltage point
back to utility source
when selectingSBU
priority” or Solar first
in program 01.
22.0V
22.5V
23.0V (default)
23.5V

Related product manuals