EasyManua.ls Logo

CSZ MicroClimate Series - Page 39

CSZ MicroClimate Series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GENERAL DESCRIPTION
Page 2-23
Model MCH-3-1.5-1.5-H/AC
MC - MicroClimate with Humidity
3 - 3 Cubic Ft. (85 L)
1-1 - 1HP HFC-404A, 1HP R-508B Cascade Refrigeration System
H/AC - Hermetic Compressor, Integral Air Cooled Condenser
Temperature Range: -70°C to +190°C (-94°F to +375°F)
Humidity Range: 10% to 95% RH
Control: ±0.5°C, ±4% RH at steady state conditions after stabilization
Temperature Performance: Temperature pull-down from:
+24°C (+75°F) to -40°C (-40°F) in 10 minutes
+24°C (+75°F) to -54°C (-65°F) in 12 minutes
+24°C (+75°F) to -68°C (-90°F) in 20 minutes
+85°C (185°F) to -40°C (-40°F) in 20 minutes
Temperature heat-up from:
+24°C (+75°F) to +93°C (+200°F) in 2.5 minutes
+24°C (+75°F) to +190°C (+375°F) in 10 minutes
-34°C (-30°F) to +24°C (+75°F) in 3.5 minutes
-68°C (-90°F) to +24°C (+75°F) In 4 minutes
Live Load Capacity: 800 watts at -40°C (-40°F)
500 watts at -54°C (-65°F)
200 watts at -68°C (-90°F)
Interior Dimensions: 17"W x 17"D x 18"H (43.2cm x 43.2cm x 45.7 cm)
Exterior Dimensions: 27.5"W x 38.75"D x 65.5"H (70cm x 98.43cm x 166 cm)
Ship Weight: Approximately 700 pounds/318 kilograms
Heat Rejection: Approximately 4,688 watts (16,000 BTU/hr) maximum during cooling
operation.
Utility Requirements: 400Y/277 VAC, 3 Phase, 50 Hertz
25 amp minimum service
Included Accessories: - 3” Access Port centered in left hand side
- Shelf Supports
- Refrigeration Service Taps
Included Instruments: - EZT-430S Controller

Table of Contents