Copyright © 2017 Cyber Power Systems, Inc.
*)200V are derated by 20%, 208 V are derated by 10% for OL6000RT3U
200, 208, 220, 230, 240Vac (Configurable) ±2%
50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz
Transfer Time (Typically)
THD < 3% at Linear Load, < 5% at Non-linear Load
ECO Mode Bypass Voltage Range
±10%, ±15% (Configurable)
(3) L6-30R, (1) Terminal block
IEC 61000-4-5 Level 3 (2430 Joules)
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Line Mode: 105~125% Load for 1 min, 126~150% Load for 10 sec
Battery Mode: 105~130% Load for 10 sec, 131~150% Load for 2 sec
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Recharge Time 0-90% (Typical)
Multi-Function LCD Readout that Supports:
Multi-Language Interface, (19) Types of Read Out,
(24) Types of Function Setting, (3) Event Logs
Power On (White), Line Mode (Green), Battery Mode (Yellow),
Bypass Mode (Yellow), Fault (Red), Replace Battery (Red)
Battery Mode, Battery Low, Overload, UPS Fault
Operating Relative Humidity
Start-up Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
(1) Serial Port (RS232), (1) USB Port, (1) Relay Out
(1) Expansion Slot for optional remote management cards
Power Management Software
PowerPanel
®
Business Edition
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Dimensions--Battery Module
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Net Weight--Battery Module
CE, UL1778, FCC part 15 Class A