TECHNICAL SPECIFICATIONS
14
Model
OLS1000EC/XL OLS2000EC/XL OLS3000EC
OLS3000ECa/
XL
Configuration
Capacity (VA) 1000VA 2000VA 3000VA 3000VA
Capacity (Watts) 800W 1600W 2400W 2400W
Form Factor Tower
Energy-saving Technology
Yes, ECO Mode Efficiency 95%
Input
Input Voltage Range
110~300Vac ± 5% for 1000/2000/3000VA model @ 0~50% Load ± 5%
120~300Vac
±
5% for 1000/2000VA model
140~300Vac ± 5% for 3000VA only
@ 50~60%Load ± 5%
140~300Vac
±
5% for 1000/2000VA model
160~300Vac ± 5% for 3000VA only
@ 60~80%Load ± 5%
160~300Vac
±
5% for 1000/2000VA model
190~300Vac ± 5% for 3000VA only
@80~100%Load ±5%
Input Frequency Range 40~70Hz
Input Power Factor 0.98
Cold Start Yes
Output
Output Waveform Pure Sine Wave
Output Voltage 208, 220, 230, 240Vac ±1%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz *
Transfer Time (Typically) 0ms
Rated Power Factor 0.8
Harmonic Distortion THD < 3% at Linear Load, < 5% at Non-linear Load @ Nominal Input
Crest Factor 3 : 1
ECO Mode Voltage
Regulation
±10%, ±15% (Configurable)
UPS Outlets
(3) IN or IEC C13
(3) IN +(1) Terminal
Block or (3) IEC
C13
(4) IEC C13+(1)
Terminal Block
(3) IN+(1)
Terminal Block or
IEC C13+(1)
Terminal Block
Protection
Overload Protection
Line Mode 105~110% Overload warning only (No shutdown)
, 110~120% Warning, transfer to bypass after 60s
>120% Transfer to bypass immediately
Battery Mode 105~110%
Overload warning only (No shutdown)
, 110~120% Warning, shutdown after 10s
>120% Shutdown immediately
Bypass Mode 130~110% Warning only
>130% Shutdown immediately
Short Circuit Protection UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
Specifications
(2) 12V/7AH (4) 12V/7AH (6) 12V/9AH (6) 12V/7AH
For -EXL Models, NO Battery Inside.
Recharge Time (Typically) 4 Hours (inside batteries)
Sealed, Maintenance Free Yes
Status Indicators
LED Screen Graphic LED
Audible Alarms
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Charger Failure /Over Charged, Fan failure
Environment
Operating Temperature
32 to 104 ( 0 to 40)
Operating Relative Humidity 20 to 90% Non-Condensing
Management
On-Device Features Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports (1) Serial Port (RS232)