6
High
Transfer
Voltage
253V-271V 257V In Local Power Quality
settings, 10 fixed
voltage ranges can be
chosen. However, you
can fine tune the High
Transfer Voltage in this
function.
If the utility voltage is
usually high, and the
connected equipment
can work in this
condition, you can set
the output voltage
range higher to reduce
the UPS from going to
Battery Mode as often.
Low
Transfer
Voltage
189V-207V 195V In Local Power Quality
settings, 10 fixed
voltage ranges can be
chosen. However, you
can fine tune the Low
Transfer Voltage in this
function.
If the utility voltage is
usually low, and the
connected equipment
can work in this
condition, you can set
the output voltage
range lower to reduce
the UPS from going to
AVR Mode or Battery
Mode as often.
Sensitivity Low
▄ Normal
▅▆ High
Normal If the connected
equipment can tolerate
more power events
(Example: unstable
power often associated
with stormy weather),
select Low Sensitivity.
The UPS will go to
Battery Mode less
often. If the connected
equipment is more
sensitive to power
events, select High
Sensitivity. The UPS
will go to Battery Mode
more often.
Low Battery
Warning
5/6/7/8 mins 5 mins The audible alarm will
continuously beep
when the remaining
runtime is less than the
selected value.