Checking the thermostats
Plot or scan tables for pressure, setpoint and ambient values for each WPT installed.
Do the values make sense?
DA --> Ambient above setpoint, pressure should be above the calibration pressure
RA --> Ambient above setpoint, pressure should be below the calibration pressure6
Are all WPTs showing battery life of OK?
Have the all the WPTs been calibrated?5
Validate hop count. Make sure no more than 6 repeaters are needed for any WPT4
Validate thermostat count for Repeaters and Husbs. Do any exceed 15?3
Do the RSSI statistics from the Node Status page show good links for all nodes?
RSSI greater than 3 for last 24HR, current RSSI greater than 3 for all hops2
Have all thermostats reported in the last 15min1
ResultsInstallation ChecklistItem #