139
Cypress Confidential
Accessing WPT using BACnet/IP
Each WPT is represented as a BACnet Device.
Conventional WPT devices support the following I/O Objects
- 3 x Analog Inputs (Ambient Temp, Branch Pressure and Battery Level)
- 2 x Analog Outputs (Setpoint, Unoccupied Setpoint)
- 1 x Binary Input (Occupancy Override)
- 1 x Binary Output (Occupancy State)
Deadband WPT devices support the following I/O Objects
- 3 x Analog Input Object (Ambient Temp, Branch Pressure and Battery Level)
- 4 x Analog Outputs (Setpoint HeatBelow/CoolAbove, Unoccupied Setpoint
HeatBelow/CoolAbove)
- 1 x Binary Input (Occupancy Override)
- 1 x Binary Output (Occupancy State)
WPT BACnet Gateway is BBMD enabled.