140
Cypress Confidential
BMS Integration via BACnet
GBC configuration
- Every node must have a network wide, unique
BACnet ID assigned.
- All schedules must be disabled as they will
conflict with BACnet generated
setpoint/occupancy changes.
- BACnet Virtual Network ID must be unique for all
servers on the network. Allows clients to
identify BACnet servers.