Troubleshooting for Outdoor Unit SiUS121630EA
178 Service Diagnosis
7.13 High Pressure Control in Cooling
Error Code
F6
Outdoor Unit LED
Display
A
j
1
i
2
h
3
i
4
i
5
h
Method of Error
Detection
High pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above about
65
°C
(149°F).
The error is cleared when the temperature drops below about
49.5
°C (121.1°F).
Supposed
Causes
The installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Troubleshooting
Check No.01
Refer to P.191
Check No.12
Refer to P.194
Check No.17
Refer to P.198
Check No.18
Refer to P.198
Check No.19
Refer to P.199
(R20418)
Caution
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.
Check No. 17
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Other manuals for Daikin 4MXS36NMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 4MXS36NMVJU and is the answer not in the manual?

Daikin 4MXS36NMVJU Specifications

General IconGeneral
Model4MXS36NMVJU
CategoryAir Conditioner
Heating Seasonal Performance Factor (HSPF)4.0
Number of Connectable Indoor Units4
Seasonal Energy Efficiency Ratio (SEER)6.0
RefrigerantR32
Indoor Units CompatibilityCompatible with various indoor units
Indoor Unit Dimensions (HxWxD)Varies by model
Indoor Unit WeightVaries depending on the connected indoor unit model
Operating Temperature (Cooling)-10 to 46 °C
Operating Temperature (Heating)-15 to 24 °C
TypeMulti-Split System

Related product manuals