5 Application guidelines
Installer reference guide
15
EBLQ+EDLQ011~016CAV3+W1 + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
#: [A.2.2.E.5]
Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
Wireless. The Daikin external room thermostat is available in a
wireless version.
Efficiency. Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heatpump system.
Comfort. In case of under floor heating, the wireless external
room thermostat prevents condensation on the floor during cooling
operation by measuring the room humidity.
Heatpump convectors
Setup
B
A
d
a
b
c
A Main leaving water temperature zone
B One single room
a User interface
b Control box
c Backup heater (option)
d Remote controller of the heatpump convectors
The heat pump convectors are directly connected to the outdoor
unit – or to the backup heater, if there is one.
The desired room temperature is set via the remote controller of
the heatpump convectors.
The space heating/cooling demand signal is sent to one digital
input on control box EKCB07CAV3 (X2M/1 and X2M/2)
The space operation mode is sent to the heatpump convectors by
one digital output on control box EKCB07CAV3 (X8M/6 and
X8M/7).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heatpump convectors.
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
#: [A.2.2.E.5]
Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink
function.
Stylish.
Combination: Underfloor heating + Heatpump
convectors
Space heating is provided by:
The underfloor heating
The heatpump convectors
Space cooling is provided by the heatpump convectors only. The
underfloor heating is shut off by the shut-off valve.
Setup
B
A
d
M1
a
b
c
A Main leaving water temperature zone
B One single room
a User interface
b Control box
c Backup heater (option)
d Remote controller of the heatpump convectors
The heat pump convectors are directly connected to the outdoor
unit – or to the backup heater, if there is one.
A shut-off valve (field supply) is installed before the under floor
heating to prevent condensation on the floor during cooling
operation.
The desired room temperature is set via the remote controller of
the heatpump convectors.
The space heating/cooling demand signal is sent to one digital
input on control box EKCB07CAV3 (X2M/1 and X2M/2)